Summary
- A power transformer has no impedance, only a percentage of a base the unit carries with it; the base moves when a cooling stage is switched on, and the percentage moves with it while the copper does not.
- Hitachi Energy's own efficiency product-information sheet labels its impedance row "on the rated tap" and names no apparent power; its own slide prints 40/60 MVA ONAN/ONAF beside 14 % and leaves the base unstated. Read on the two possible bases, that one number is 21 % or 9.33 %, and the fault current at the 132 kV terminals is 1,874 or 1,250 amperes.
- Two purchaser documents each name a base, and both name the fan-off stage rather than the highest assigned power that the standard calls the rated power. The default and the practice disagree, and the reader supplies the difference.
The percentage is a ratio, and the denominator travels inside the tank
IEC 60076-1 defines the quantity precisely: relative short-circuit impedance z = 100·Z/Zref, with Zref = U²/Sr, where Sr is the reference value of rated power (IEC 60076-1, edition 2.1). The ohms are physical — copper, leakage flux, the geometry of the core window. The percentage is that physical thing divided by a base that lives in the same box. Change the base and the percentage changes while nothing physical has happened.
Which base? The standard settles it in the direction that makes the ambiguity stranger rather than smaller. Where different values of apparent power are assigned under different circumstances, for example with different methods of cooling, the highest of those values is the rated power (BS EN 60076-1:2011). The fan-cooled rating is the rated power; the fan-off rating is an assignment below it. And the same standard's rating-plate clause lets the lower stage be printed as a fraction of the rated power, its worked example being ONAN/ONAF 70/100 %.
So one set of windings carries a top number and, optionally, a schedule of fractions of it. A percentage impedance referred to "the rated power" therefore refers to the top of the ladder — provided the reader knows the rule. The standard is candid that many do not. Its clause 5.5 observes that percentage values "may lead to confusion because of varying practices concerning reference values", and advises that the corresponding reference power and reference voltage be explicitly indicated every time percentages are given. Standards do not write that sentence about settled matters.
The manufacturer names the tap and not the megavolt-ampere
Here is what Hitachi Energy publishes for the European efficiency rules: a product-information table whose columns are rated power in megavolt-amperes — 12.5, 20, 31.5, 40, 50, 63, 85, 100 — and whose rows include one labelled Short-circuit impedance on the rated tap (%) (EU Ecodesign product information). The row names the tap. It does not name the apparent power, and the sheet prints no cooling-class ladder beside it. It does print a cooling row — the power absorbed by the portion of the cooling system that is permanently on, normally the first stage — with a note that for the ONAN rating that figure is zero. The document knows about cooling stages. It keeps them away from the impedance.
One reading caveat, stated plainly: the extracted table came back with its columns out of order, and the alignment of individual impedance values to individual MVA columns is not reliable in the text I could read. No claim below depends on it. What the sheet says about itself is what the row label says — the percentage is taken on a tap, and the power it is a percentage of is left to the reader.
The presentation slide goes one step further and stays silent at the same point. 40/60 MVA is a ladder: 60 with both banks of fans running, 40 with none. 14 % sits beside it. Put that fourteen on the top of the ladder and the same winding prints 21 % on the fan-off rating, because 14 × 60 ÷ 40 = 21. Put it on the fan-off rating and the same winding prints 9.33 % on the top, because 14 × 40 ÷ 60 = 9.33. Both figures are mine, from two numbers printed on one slide, and they differ by a factor of 2.25.
The ohms do not move, so the current does not move either
Take the slide's numbers and put the fourteen per cent on the 60 MVA base, where the standard's rule says a rated power lives. At 132 kV the reference impedance is 132² ÷ 60 = 290.4 ohms, so the impedance is 0.14 × 290.4 = 40.66 ohms, and the fault current at the terminals — transformer impedance alone, no system impedance — is 132,000 ÷ (√3 × 40.66) = 1,874 amperes. The other route gives the same answer: rated current is 60,000 ÷ (√3 × 132) = 262.4 amperes, and 262.4 ÷ 0.14 = 1,874 amperes. That division is mine; both operands are printed on the slide.
Now do it with the base swapped, as a reader might who takes the 40 MVA stage for the reference: 0.14 × (132² ÷ 40) = 60.98 ohms, and 132,000 ÷ (√3 × 60.98) = 1,250 amperes. A reader who assigns the fourteen per cent to the wrong stage understates the current his switchgear must interrupt by 40 ÷ 60, which is a third. The copper has not changed. Two readings of one sentence differ by 624 amperes at the same bus.
The direction of the error is the uncomfortable part. Taking the percentage to belong to the lower rating yields a larger impedance and a smaller current, so the breaker looks adequate until the fault arrives. A third is not a rounding difference in an equipment rating; it is the distance between a specification and a repair.
The tolerance band is not the size I first assumed, and it is not a paralleling rule
My own opening premise for this piece had the tolerance backwards, so here is the correction rather than a tidier version of the first guess.
Table 1 of IEC 60076-1, for two separate windings on the principal tapping, sets the permitted deviation on a declared short-circuit impedance at ±7.5 % where the impedance is 10 % or more and ±10 % where it is below 10 %; other tappings carry ±10 % and ±15 %; an auto-connected pair or a second pair carries ±10 % (Tiza Group on transformer tolerances, corroborated by Amperis' test calculator to the same standard). At 14 % the wider band applies: 12.95 % to 15.05 %.
On that band the fault current runs from 1,874 × (14.00 ÷ 15.05) = 1,744 amperes at the high-impedance edge to 1,874 × (14.00 ÷ 12.95) = 2,027 amperes at the low-impedance edge. Mine, from the band and the nominal current. One nameplate statement, honestly compliant across its whole spread, is a 283-ampere spread in the current the plant must survive.
The rule that decides whether two units may be operated together turns out not to be a rule with a number in it. The conditions, as an IEC-based technical guide summarises them, are the same phase-angle relation, the same ratio within tolerance and a similar tapping range, and the same relative short-circuit impedance "with some tolerance"; the guide adds that units differing by more than about 1:2 should not be combined (Medium Voltage technical guide, 2017). Some tolerance.
The familiar ten per cent is practice, not a clause. An application note from A. Eberle lists "the same relative short-circuit impedances (value Δ uk = < 10 %)" as a condition and then says the maximum permissible difference depends on the acceptable negative effects and on the transformer load factor (Info Letter No. 13). That is a practitioner's judgement wearing a decimal point.
The 40/60 ladder is 1.5:1, comfortably inside the 1:2 advisory ceiling, so this is not the pairing the guide warns against — and its percentage still cannot be placed on either stage from the slide alone.
Now put the band and the load sharing together and the trap closes from the manufacturing side. Two 60 MVA units, each individually compliant at opposite edges of the tolerance, at 12.95 % and 15.05 %, share load in inverse proportion to their relative impedances. The lower-impedance unit carries 15.05 ÷ (12.95 + 15.05) = 53.75 % of whatever the pair carries, so the pair reaches one unit's full 60 MVA at 60 ÷ 0.5375 = 111.6 MVA between them, leaving 8.4 MVA of the 120 MVA nameplate unusable, about 7.0 %.
That arithmetic is mine, and it assumes what the guide asks for — identical ratios, ratings and phase displacement — which is precisely the assumption a real order cannot verify from the documents in this set.
Nothing in that calculation is a defect. Both transformers are good. The tolerance is the tolerance; the load sharing is Ohm's law. What the two numbers do not come with is each other.
What the unit must survive, and for how long
The number that turns a percentage into amperes has its own standard, worth quoting because a widely repeated sentence gets it wrong. IEC 60076-5 computes short-circuit current as I = U/(√3·(Zt+Zs)) with Zt = zt·Ur²/(100·Sr) — the measured impedance in per cent at rated current, referred to the rated power in megavolt-amperes — and fixes the duration of the current used for the thermal withstand calculation at 2 seconds unless a different duration is specified, with shorter durations by agreement for auto-transformers and where the short-circuit current exceeds 25 times rated current (IEC 60076-5:2006 preview). The Indian national adoption carries both rules, which is a useful corroboration because it was read from a different host (IS 2026-5:2011).
The often-quoted "1.5 times rated current for 2 seconds" is not in that standard. It appears on a distribution-transformer vendor's product page describing factory routine testing (a 50 kVA oil-immersed unit). For a transformer with 10 % impedance the short-circuit current is roughly ten times rated current; a 1.5-times test would demonstrate little about it. The multiple of rated current is not a test setting at all. It is one divided by the percentage, and therefore it inherits the percentage's base.
Three documents in the wild that name a base, and they name the other one
Two purchasers do what the manufacturer's sheet and slide leave undone, and both pick the fan-off stage.
A spec sheet for a 30/40/50 MVA ONAN/ONAF/ONAF unit walks the whole ladder — 30 MVA without fans, 40 with stage one, 50 with both — and then says "Impedance (@ 30 MVA): 12-15%" (Larson Electronics spec sheet 310716). A purchaser's specification for a 115/144/180 MVA-class unit rated ONAN/ONAF/ONAF states the HV–LV impedance as "9.0 % +/- 7.5% ONAN rating" (AES main power transformer specification).
The Larson base is the lowest number in its own ladder, which under the IEC rule is not the rated power. Re-base its band onto the other stages and it moves: 12–15 % at 30 MVA becomes 9.0–11.25 % at 40 MVA and 7.2–9.0 % at 50 MVA. Those divisions are mine, from its own printed band and its own printed ladder, and they are why a buyer comparing two makers' impedance columns is comparing two numbers on two bases unless both pages name the MVA.
This is not a manufacturer conspiracy. It is a convention collision, documented in the open, and the people doing the work report it as such: a long-running engineering forum thread has practitioners taking a 32/40 MVA ONAN/ONAF unit's 12 % on the 32 MVA base and on the 40 MVA base in the same discussion, quoting the same clauses at each other (Impedance on IEC transformer nameplate).
The same megavolt-ampere, graded from Brussels
One more document makes the missing denominator more than an engineering inconvenience. Commission Regulation (EU) No 548/2014 grades large power transformers by a Peak Efficiency Index, and its Annex I Table I.7 states the minimum against "Rated Power (MVA)". The calculation uses Sr, "the rated power of the transformer or autotransformer on which Pk is based", and kPEI, "the load factor at which Peak Efficiency Index occurs"; product information must state the PEI and the power at which it occurs; intermediate ratings are interpolated (Regulation (EU) No 548/2014). The 2019 amendment adds 125, 160 and ≥200 MVA rows, sets Tier 2 minima of 99.780 %, 99.790 % and 99.797 %, and states that for ONAN and ONAN/ONAF cooling systems Pc0 is always zero and for ONAN systems Pck is always zero (Commission Regulation (EU) 2019/1783).
So the regulator's grading base is the same apparent power the impedance percentage is a percentage of. At 100 MVA the two tiers' minima, 99.737 % and 99.770 %, differ by 0.033 percentage points, which — taking the index at face value as the regulation writes it — is the difference between permitting 263 kW and 230 kW of electrical loss at that rating. My subtraction, on the regulation's own two figures.
The manufacturer whose product-information sheet opened this article is the one this amounts to a disclosure duty for. It publishes the sheet. The sheet names the tap. What it does not name is the one word that would let a reader join its impedance row to its efficiency row: which megavolt-ampere.
Nine fields, one at a time
| Field | What a reader needs printed beside it | Who in this set printed it |
|---|---|---|
| Rated power across cooling stages | at least two apparent powers and the class of each | Hitachi Energy slide: 40/60 MVA ONAN/ONAF; Larson: 30/40/50 MVA ONAN/ONAF/ONAF |
| Cooling-class ladder as row labels | ONAN, ONAF, OFAF naming each row rather than a footnote | Larson and AES name the classes in the rating line |
| Impedance percentage | the declared short-circuit impedance in per cent | Hitachi Energy sheet; Hitachi Energy slide; Larson; AES |
| The base that percentage refers to | the MVA on which the percentage is calculated | Larson (30 MVA) and AES (ONAN rating) only |
| Tap and reference condition | which tap, and any reference temperature | Hitachi Energy sheet says "on the rated tap" and nothing more |
| Tolerance on the declared value | the band in per cent, or the class | Table 1 through two secondary reproductions; no manufacturer page here |
| Parallel-operation criterion | the permitted impedance difference between two units | no numeric criterion found; IEC-derived text says "some tolerance", A. Eberle says under 10 % as practice |
| Short-circuit withstand | the current and its duration | IEC 60076-5 and the Indian adoption: 2 s |
| The division itself | percentage converted to ohms for a named unit | no page in the set performs it |
Nine fields. The manufacturer's own two surfaces carry three of them cleanly, four partially, and miss the division entirely. A reader who wants the fault current at that 132 kV bus supplies the base from the standard, the tolerance from a secondary reproduction, the paralleling judgement from an application note, and the division from his own calculator.
What this costs, and to whom
The engineer is the obvious loser and the least interesting one, because he does this for a living and asks. The expensive case is the interface where nobody asks: a switchgear package bought against one document, a relay setting calculated by a different team from a different sheet, a protection study that says "14 % on 60 MVA" in a footnote nobody reads — and then an uprating, pumps on, second fan bank commissioned, which raises the published apparent power of the same windings and, on any page that reprints the impedance, changes the percentage without touching the copper.
Every relay set from the earlier print is then wrong by exactly the ratio of the two ratings, and nothing in the plant has moved.
The institutional consequence is quieter. A regulator grading efficiency in apparent power is grading on the number the impedance percentage is a percentage of. The best-efficiency point and the fault level of the same machine are referred to one quantity, and that quantity is not printed on the page a buyer reads first. It is printed, in percentages, on the plate. Somewhere behind the percentages there is a ladder, and the ladder is the number.
Hitachi Energy's TrafoStar page notes that the company has the largest number of transformers that have passed short-circuit tests in independent laboratories, and that the experience is integrated into the platform (TrafoStar). A manufacturer that has tested more short circuits than anyone has the least excuse for leaving the base of the percentage unstated. The sheet is one word short of complete, and the word is a cooling class.
What I did not find, over seventeen documents
Bounded, and dated 26 November 2026. Across the seventeen documents listed below: none prints a percentage impedance beside the apparent power it refers to and the cooling stage that power belongs to, in one row. The one statement carrying a ladder and a percentage names no base; the two documents that name a base print no per-stage ladder beside it. No Hitachi Energy document in the set prints a per-stage MVA ladder with an impedance beside it. No document prints the ohmic impedance alongside the percentage for the same unit.
No document prints the tolerance applicable to the impedance it declares: the Larson sheet gives a 12–15 % bandwidth and the AES sheet ±7.5 %, and neither cites the table. No document prints a paralleling criterion and a manufacturing tolerance on the same page. The Hitachi Energy efficiency sheet names no cooling class for its impedance row. No reviewed page gives a reference temperature with the impedance; the only qualifiers are the principal tapping and the rated tap. No reviewed page performs the percentage-to-ohms division in public. No reviewed page prints a short-circuit withstand current for a named unit.
Three reading limits travel with that. The standard itself was read through two third-party copies rather than the official IEC webstore publication; the tolerance table through two secondary reproductions of it; the second standard's parallel-operation clause through an IEC-based technical guide rather than its own text. The European regulation's content came from its ELI address because the CELEX HTML address supplied did not return readable text. And no nameplate photograph was read: both documents that name a base are purchaser or vendor sheets, not plates.
The Hitachi Energy directory entry records the entity this reading is filed against. The documents cited are published under the Hitachi Energy name; which legal entity in the group produced each one is not claimed here.
The number is real. The sentence is incomplete.
Fourteen per cent is not vague. It is exact, it is tested, and it is printed by a company that has short-circuited more transformers in independent laboratories than any competitor. What is missing is five characters of context: which megavolt-ampere.
A transformer has no impedance in the sense a reader expects. It has a ratio to a base it carries with it, and the base is a ladder, with a first rung where the fans are off and a top rung where they are on. Print the ratio and the ladder in one line and the whole downstream arithmetic falls out: the fault current, the relay curve, the load sharing between two good units, the efficiency grade. Print the ratio alone and every one of those figures is an assumption a stranger has to make, silently, at the point where being wrong is most expensive.
Sources, in the order this article first leans on them. Hitachi Energy circularity presentation, September 2025 · IEC 60076-1 edition 2.1 · BS EN 60076-1:2011 · Hitachi Energy EU Ecodesign product information sheet · Tiza Group, transformer tolerances · Amperis, test calculator to IEC 60076-1 · Medium Voltage technical guide, 2017 · A. Eberle, Info Letter No. 13 · IEC 60076-5:2006 preview · IS 2026-5:2011 · Larson Electronics spec sheet 310716 · AES main power transformer specification sheet · Eng-Tips, impedance on IEC transformer nameplate · Regulation (EU) No 548/2014 · Commission Regulation (EU) 2019/1783 · Hitachi Energy TrafoStar · 50 kVA oil-immersed transformer page · Hitachi Energy Holdings Ltd in the BTW directory
An earlier BTW briefing on this manufacturer, published the same day, took its 100 MVA nameplate and asked why the European efficiency regulation grades in apparent power while the data centre pays in megawatts. This piece takes the same megavolt-ampere as a denominator rather than as a missing temperature, and asks the question one clause further back: which of the unit's several apparent powers the number belongs to.
Member Briefing
Read the full trend briefing
Members read the full briefing with the source notes behind every finding.
Strategic Circle
A daily briefing in your language, built from changes we have verified.
Join for USD 20/monthCancel anytime.
Members also get the full research library, a daily briefing on the networks they follow and the private forum.