Summary
- On every APC rack power distribution unit sheet read for this briefing, the printed inlet current is the standard rating of the plug the unit is fitted with: 10 A for an IEC 60320 C14 inlet, 16 A and 32 A for the corresponding IEC 60309 connectors.
- The printed load capacity is that current multiplied by nominal voltage — 2,300 VA for 10 A at 230 V, 22,000 VA for 32 A at 400 V three-phase, sold as a "22 kW" unit — and no rack PDU sheet in the set prints the power factor that would make it a wattage.
A rating that belongs to the plug
The specification table for the APC NetShelter Basic Rack PDU AP9568 is four lines long. Zero U, 10 A, 230 V, fifteen IEC 60320 C13 outlets, a C14 input. Two rows carry the electricity: "Input current limits 10 A" and "Load Capacity 2300 VA". The outlet row gives a connector type and a quantity, not an amperage and certainly not a sum (AP9568 product page).
That 10 A is not a measurement of the box behind the panel. It is the rating of the connector on the end of the cord. IEC 60320-1 puts C13 at 10 A and its C14 inlet mate at 10 A, C19 at 16 A and C20 at 16 A (the IEC 60320-1 combination table). Schneider Electric's own connector paper repeats the pair in plain words — the C13/C14 type "has a rating of 10 amps" — and adds the North American twist, that UL limits draw to 80 per cent of the connector rating (White Paper 20, revision 2).
The count of amperes on a sheet is therefore inherited. Follow the cord types up the range and the inheritance is visible: the AP7920 prints "[In] rated current 12 A" and an "Input current limits" of 15 A beside "Max current draw 10 A" and a 2,300 VA load capacity, on a page that also names its C14 inlet and a 6.50 ft cord (AP7920 datasheet). Four current-related figures and one volt-ampere figure on one page, none of them a quantity a meter produced.
At the top of the three-phase range the inheritance is cleaner still. The AP8886, sold as a "22kW 230V 32A" metered unit with thirty C13 and twelve C19 outlets, prints a "Max line current" of 32 A and an input connection of "IEC 60309 32 A 3P + N + E" (AP8886 datasheet). The AP8881, sold as "11kW 230V 16A" with thirty-six C13 and six C19, prints a line rated current of 16 A and a plug of "IEC 60309 16 A 3P+N+PE" (AP8881 datasheet). Thirty-two amperes is what a 32 A connector carries; sixteen is what a 16 A connector carries. The datasheet is telling you the standard, and dressing it as a specification.
The volt-ampere is the ampere times the volts
Run the multiplication. Ten amperes at 230 volts is 2,300 VA, which is the AP9568's load capacity to the digit. Thirty-two amperes at 400 volts three-phase is 22,170 VA, printed on the AP8886 as 22,000 VA. Sixteen amperes at 400 volts three-phase is 11,085 VA, printed on the AP8881 as 11,000 VA. Thirty-two amperes at 230 volts is 7,360 VA, printed on the APDU9953 sheet as a 7,400 VA load capacity and in the long specification guide for the same unit as "7.4 kW input power" (APDU9953 datasheet).
Nothing in that ladder involves a power factor other than one, because multiplying amperes by volts gives volt-amperes by definition. The trick is that the same number then gets a kilowatt's name. The word on the box is 22 kW; the field on the sheet is 22,000 VA; the arithmetic that connects them is a factor of exactly one, printed nowhere and correct only if the servers behind the strip draw current in phase with the voltage.
The paper's kilowatt
The conversion from the rented unit to the printed one lives in a selection document, Schneider Electric's White Paper 202 on choosing IT rack power distribution, version 2, dated 19 January 2024. Its table of continuous capacity by input voltage, phase and cord amperage is exactly the join the datasheets omit: it "maps a total continuous kW capacity to the required rPDU input cord amperage" (White Paper 202 v2).
Read the cells and the whole table falls to one expression. A 30 A whip carries 2.9 kW at 120 V, 5.0 at 208 V single-phase, 5.8 at 240 V single-phase, 8.6 at 208 V three-phase and 17.3 at 415 V three-phase. A 20 A whip carries 1.9, 3.3, 3.8, 5.8 and 11.5 kW on the same ladder (a second copy of the same table). Put every cell through volts times amperes, times the square root of three where the row is three-phase, times 0.80, and all ten close: 208 × 30 × 0.80 = 4,992 W for the single-phase case the paper prints as 4.99 kW in its own Table 1A, and 208 × 30 × 1.732 × 0.80 = 8,646 W for the three-phase case it prints as 8.6 kW. The table is one arithmetic printed ten times, and its kilowatt is a volt-ampere with two things done to it: multiplied by the square root of three where the supply is three-phase, and multiplied by 0.80.
That 0.80 is where the interesting asymmetry lives. The paper states it in a single sentence with two halves: "Note that North American rPDUs will have 20A circuit breakers and are derated to 80% (16A) while Europe will have 16A circuit breakers, not derated (i.e., 100% rated)." A 20 A-rated unit "should only be operated at 16A", and IEC-region units are "not required to be derated". Do the two halves together and the same breaker carries different steady current on each side of the Atlantic: a 16 A breaker permits 16 A continuously in Europe and 12.8 A in North America, twenty-five per cent more permitted load from the same copper (mine). The origin of the factor is a code sentence rather than a preference — branch-circuit conductors must have an ampacity "not less than the noncontinuous load plus 125 percent of the continuous load", with Exception 1 allowing 100-per-cent-rated assemblies the whole rating, and the same 125 per cent applies to the overcurrent device (NEC 210.19(A)(1), and some commentary on the current edition).
The datasheet layer never says any of this. One Schneider marketplace listing puts the two numbers side by side without a word of explanation: "Input current limits 20 A" and "Line Rated Current 16 A" for the same strip, alongside a 2,300 VA load capacity and a 20 A maximum current draw (the marketplace listing). The words "80%" and "continuous load" do not appear on the page. A reader who knows the code can see the derating in the pair of numbers. A reader who does not learns that his strip has a 20 A limit, a 16 A rating and a 2,300 VA capacity, and that all three describe it.
The factor nobody prints
The first thing a buyer tries is to add the outlets. He cannot. Fifteen C13 outlets at a nominal 10 A sum to 150 A against a 10 A inlet. Twenty-one C13 and three C19 on the APDU9953 sum to 258 A against 32 A. Thirty C13 and twelve C19 on the AP8886 sum to 492 A against 32 A. Thirty-six C13 and six C19 on the AP8881 sum to 456 A against 16 A, which is twenty-eight times its own inlet (mine). The per-outlet amperes, where they exist at all, live in the long specification guide and not in the datasheet: the 9000 Series guide prints "Maximum output current (outlet) 10A (C13), 16A (C19)" and a per-bank input limit of 16 A, and it is the only page in the set that does (the 9000 Series overview and specifications).
The second thing he tries is the cord. Seventeen documents were read for this briefing and not one prints the conductor gauge of the input cord, though most print its length and all print its plug. The breaker is worse than absent; it is a category label. One distributor copy of the AP8881 sheet prints "Protection Type: Without circuit breaker" where a copy of the AP8886 sheet prints "Protection type: Circuit breaker" (the AP8881 copy, the AP8886 copy). The long 9000 Series guide gets as far as "two (2) 16A, single–pole circuit breakers" and stops: no construction type, no trip curve, no short-circuit interrupting rating, so a reader cannot tell a thermal-magnetic breaker from a hydraulic one, and cannot tell which the strip in front of him holds.
The third thing he tries is the factor that turns volt-amperes into watts, and this is the one the company already knows. The rack PDU's own user guide lists among the quantities its meter reports "Device power, peak power, apparent power, power factor and energy" (the AP88 series user guide). Power factor is measured continuously by the device. It is printed as a specification for the neighbouring product line, where a Smart-UPS technical specification states flatly that "The input power factor is >.95" (the UPS specification). And it is printed for no rack PDU in this set. The number exists on the meter, exists on the UPS sheet, and has no place on the strip's own page.
So the table's kilowatt is a wattage only if the load is resistive. At a power factor of 0.9 the 8.6 kW cell is 7.8 kW; at 0.8 it is 6.9 kW (mine). Schneider Electric builds and sells the strip; the operator owns the rack, the servers and the power factor that decides which of those numbers the customer actually gets. The vendor prints the permission, the customer supplies the conversion, and the document that would settle it is already bolted to the strip, reading a quantity nobody writes down.
What a buyer can check
Three questions, in the order the electrons meet them.
Which amperes does the breaker protect — the plug's, the inlet's, the bank's, or the derated continuous figure, and which of the four numbers on the sheet is it? At what fraction of those amperes is continuous load permitted, and does the page cite the rule or leave it in a white paper? And whose power factor sits in the multiplication that turns the strip's capacity into the kilowatts on the contract?
The AP9568's equipment schedule on the BTW directory entry for Schneider Electric Industries SAS will not answer them. The strip will, eventually, by tripping. A rack is rented in kilowatts and protected in amperes, and the device in the middle is rated by its plug, counts its capacity in a unit multiplied by one, and measures the factor it does not print.
Member Briefing
Read the full trend briefing
Members read the full briefing with the source notes behind every finding.
Strategic Circle
A daily briefing in your language, built from changes we have verified.
Join for USD 20/monthCancel anytime.
Members also get the full research library, a daily briefing on the networks they follow and the private forum.