Summary

  • Vertiv's Liebert UPS sheets print capacity as a unity pair — 400/500 kVA beside 400/500 kW, 100-250 kVA/kW, 1500 VA / 1500 W — and then accept any load from 0.7 leading to 0.4 lagging at 100 per cent of rating without derating. At full rated current into a 0.4 lagging load, the 500 kVA frame delivers 200 kW.
  • The heat row is the efficiency row converted. 61,876 BTU/h at full load divides by 3,412 BTU per kWh to 18.13 kW of loss, which returns the printed 96.5 per cent. That figure is a test-bench number measured at 1.0 power factor, and no reviewed Vertiv page prints heat at any other power factor.

One row, two numbers, one decimal

Start with the line that decides everything downstream. The Liebert EXL S1 data sheet prints "UPS Rating (kVA) 400/500" and, in the row beneath it, "Output Active Power at 104°F (40°C) (kW) 400/500" (EXL S1 data sheet). Four numbers, two of them repeated. A reader who has bought transformers for a living will recognise the shape: a kilo-volt-ampere is not a watt, and the two are equal only where the current and the voltage cross zero together, which is to say at a power factor of one.

So what is the power factor of the load this machine will be attached to? No Vertiv sheet answers that, because the answer belongs to the customer. What the sheets do instead is print a band. "Load Power Factor Supported (Without Derating) 0.7 Leading to 0.4 Lagging." The EXL S1 guide specification repeats it in the load-rating clause: 100 per cent continuous at 104°F (40°C) "for any load 0.7 leading to 0.4 lagging" (EXL S1 guide specification). Read as a capability statement, that is generous: the frame will carry its full rated current into a load anywhere in a band 1.1 wide in power factor and not flinch. Read as a buyer's arithmetic, it is a warning, because the kVA is what the frame carries and the kW is what the hall receives, and only one of those two numbers is guaranteed across the band.

The arithmetic is mine, and both operands are named. 500 kVA × 0.4 = 200 kW at the lagging end of the permitted band; 500 kVA × 0.7 = 350 kW at the leading end. The frame is printed as 500 kW. The kVA does not derate anywhere in that band. The kW the customer actually gets is his own power factor multiplied into the rating, and the sheet that prints 500 kW has no obligation to print 200.

The ampere is the apparent power

The site planning data makes the mechanism visible, because it prints the amperes in the same grid as the kVA (EXL S1 site planning data). For the 500 kVA / 500 kW frame at 480 V: rectifier AC input current 624 A nominal, 686 A maximum, recommended breaker 700 A; bypass/output current 601 A nominal with a 700 A breaker; battery 480 V, 1,294 A, 1,400 A; efficiency 96.5 per cent AC-AC at 100 per cent load and 96.4 per cent DC-AC; maximum heat dissipation at full load 61,876 BTU/h; cooling air 3,920 CFM.

Divide 500,000 by the square root of three times 480 and you get 601.4 A. That is the printed 601 A. The output ampere column on this page is the kilo-volt-ampere divided by root-three times the voltage — my division, both operands printed — and it is therefore a description of apparent power. Nothing in it moves when the load power factor changes from 1.0 to 0.4. The current at the output terminals is the same 601 A whether the customer is drawing 500 kW from it or 200 kW from it. The inverter, the cables, the output breaker and the bypass all size themselves on that current.

That is why the frame is sold in kVA: the kVA is the part of the machine that costs money.

The heat row is the efficiency row

Now the thermal side, which is where the missing decimal finally bites. Take the same row's 61,876 BTU/h at full load and divide by 3,412 BTU per kWh, the physical constant that converts one to the other. The answer is 18.13 kW of loss. Divide 500 kW by 518.13 kW of input and you return 96.50 per cent — the efficiency the same row prints as 96.5 per cent AC-AC at 100 per cent load. Both operands are printed on the page; the conversion constant is not a Vertiv figure, and applying it is my step.

That closure is the point. On this document the heat figure is not an independent measurement of what the room must remove. It is the efficiency figure, converted. And the efficiency figure carries its own definition, printed a document earlier: "Defined as output kW/input kW at 1.0 power factor load, measured at 25%, 50%, 75% and 100% of nominal load, with energy storage disconnected or at float, DC-DC converter running" (EXL S1 guide specification). Four load points, one power factor, one ambient convention. The heat row inherits all three.

So the mechanical engineer who reads 18.13 kW or 61,876 BTU/h and sizes air for it is sizing the machine's loss at unity power factor. Is that the wrong number for a 0.4 lagging load? It depends on an assumption no reviewed page resolves, and the assumption needs to be named. Hold the loss at its full-load value and the heat per delivered kilowatt goes from 18.13 ÷ 500 = 3.6 per cent to 18.13 ÷ 200 = 9.1 per cent, a factor of 2.5. That is my arithmetic on a stated assumption: the loss is set chiefly by current, and the current does not move.

Whether the loss really stays flat as the load's power factor falls is not printed anywhere in the set. Switching devices and magnetics do not care about the phase of the load, but filters and control loops are not ideal, and a converter running at 601 A into a 0.4 lagging load carries the same amperes as it does into a resistive one. The figure being held constant is defensible; the absence of a measured alternative is the finding.

Where the perimeter moves: the bypass cabinet

One document in the set does print a heat figure that does not close against the headline efficiency at all, and its own footnote explains why. The Liebert EXM site planning data pairs 100 kVA with 100 kW at 480 V input and 208 V output and prints nominal input current 133 A, maximum 152 A, recommended OPD 200 A, nominal output current 278 A with a 350 A OPD, UPS heat dissipation 18,645 BTU/h (5.5 kW), and 29,253 BTU/h (8.6 kW) with the 480:208 V transformer (EXM site planning data). The EXM table itself prints the two amperes side by side, and the APM2 planning sheet states that its nominal input current is "calculated at nominal load, 400 V input and fully charged battery": two columns, two different bases, both printed.

Check the closure. 100,000 ÷ √3 ÷ 208 = 277.6 A, which is the printed 278 A. Good: same division, different document, different voltage. Now the heat. 100 kW at 97 per cent — the brochure's double-conversion figure for the 480 V models (EXM brochure) — gives 3.09 kW of loss, which is 10,553 BTU/h. The table prints 18,645 BTU/h, a factor of 1.77 above it; and with the transformer, 8.6 kW, a factor of 2.8. The footnote on the same table says "Heat dissipation includes values for the Bypass Distribution Cabinet". So the extra is a perimeter, not an error: the table is telling the room what the room must remove, which includes the cabinet sitting in the room. The 97 per cent is telling the reader the conversion loss of a 480 V model, and this row has a 208 V output. Two perimeters, both printed, and a reader who subtracts one from the other gets a contradiction that is not there. That is a good page. It is also the only page in the set that states the perimeter of its own heat figure.

The APM2 family shows the other case, where nothing has been added. Its 30-120 kW planning sheet prints 3.6 kW of heat loss at normal load with the battery charged for the 120 kVA frame at 400 V (APM2 site planning datasheet). 3.6 ÷ 120 = 3.0 per cent of loss, so 120 ÷ 123.6 = 97.1 per cent, which closes exactly against the APM2 data sheet's own "up to 97 per cent" for the 20-120 kW frames (APM2 data sheet). Here the heat row is the efficiency row with nothing added, and the reader gets no bypass cabinet and no transformer in the number. Two Vertiv families, two different perimeters for the same physical quantity, both printed, neither labelled as the family style.

At the smallest end the part-load penalty appears. The EXM table prints 2,217 BTU/h (0.7 kW) for the 10 kVA frame. 0.7 ÷ 10 = 7 per cent of loss, so 10 ÷ 10.7 = 93.5 per cent — against 94.8 per cent implied by the 100 kVA row's own 5.5 kW, and against the brochure's 97 per cent. My arithmetic in both cases. The heat row carries a load-derating curve the single efficiency number does not.

The input ampere has a basis nobody prints

One more closure, this time on the input side. 500,000 ÷ 0.965 = 518,135 W of input real power. Divide by √3 × 480 and you get 623.2 A: the printed nominal 624 A. Divide instead by √3 × 480 × 0.99 — the input power factor the same document family prints as its minimum at full load — and the same input power is 629.5 A. Both sit below the printed 686 A maximum and the 700 A breaker, so nothing is unsafe. But the nominal column reproduces only at an input power factor of 1.0, while the same sheet prints 0.99 as the floor. Which is it? The page does not say.

That is not a defect a reader can repair by choosing the larger number; it is a stated input the breaker was sized against and it is not on the page.

The same question returns at 120 kVA on the APM2 sheet, where the printed nominal input and output currents are both 179 A. 120,000 ÷ √3 ÷ 400 = 173.2 A: the printed figure is 3.4 per cent above the division, and equals 124.0 kVA at 400 V. The page prints the basis of the input current and not the basis of the output current. Both are mine. Nothing here is wrong; something here is unstated.

Derating announced, derating quantified

Now the site conditions, where the set is lopsided in a way that costs real money. The Liebert EXM2 brochure prints a rate for altitude: 1,500 m without derating, and from 1,500 m to 3,000 m "derate power by 1% per 100 m increase" (EXM2 brochure). Apply it — my arithmetic, both operands printed — and a 250 kVA frame at 3,000 m carries 212.5 kVA, fifteen 100 m steps of one per cent each.

The same brochure prints a temperature ceiling: operates to 40°C without capacity impact, "up to 50°C with auto-derating above 40°C". No rate. The APM2 data sheet prints 0-40°C at full performance and 40-50°C "with automatic derating"; no rate (APM2 data sheet). The APM2 planning sheet prints the same pair of sentences; no rate. The ITA2 data sheet and the GXT5 brochure print no-derating ceilings at 1,500 m and 3,000 m respectively and nothing about what happens above them (ITA2 data sheet, GXT5 brochure).

So a buyer at 2,500 m and 35°C can do his own derating arithmetic and a buyer at sea level and 47°C cannot. He knows the machine carries less; he does not know how much less. At the top of the family that slack matters: one per cent of a 250 kVA frame is 2.5 kVA, and the difference between an unquantified 40-50°C band and a printed rate is a call to the factory rather than a line in a specification.

The two conditions are also never printed together. Each of temperature and altitude is stated derating-free on its own; no reviewed page states the capacity at 40°C and 3,000 m at once. The joint condition is unprinted, not prohibited. That is the sentence I would most like to see on a Vertiv sheet, and it is not on any of the eleven I read.

One more: the overload ladder on the EXL S1 data sheet — 110 per cent continuous, 125 per cent for 10 minutes, 150 per cent for 60 seconds, 200 per cent for 200 ms — is stated at 77°F (25°C), while the capacity rating above it is stated at 104°F (40°C). Two different ambients on one page, both named, and a reader who carries the 110 per cent into a 40°C room is carrying a 25°C promise into a 40°C hall.

What is not printed, counted over eleven documents

An absence is a count over named documents read on a named date, so here is the list, bounded to the eleven files cited in this article and read on 26 November 2026.

No reviewed page prints the multiplication kVA × power factor = kW, or names the power factor at which its kW column is valid. No page prints heat dissipation at a load power factor other than unity, and none prints heat at a part-load point except the EXM 10 kVA row. No page prints a quantified temperature-derating rate. No page prints the joint condition of high ambient and high altitude. No page prints the basis of its nominal input current — which efficiency and which input power factor it was computed at.

No page prints a heat figure beside the ambient and altitude at which it was measured, although the capacity rating itself is stated at 40°C. No page prints a maximum per-phase load or a capacity derating for imbalance; the only imbalance figure in the set is a voltage one, output voltage regulation under 2.0 per cent at 50 per cent unbalanced load on the EXL S1 data sheet.

And no page prints a per-phase loading table, a neutral rating for the rectifier path, or what the output neutral carries when the bypass is feeding the load — the guide specification prints a three-wire-plus-ground rectifier and a four-wire-plus-ground bypass and stops there.

Efficiency by load percentage is not evenly published either. It is a table for the EXL S1 only in the guide specification; the data sheet omits it. The EXM brochure presents it as a curve across 30-100 per cent load that the captured text describes only in fragments, and the EXM2 brochure prints a single "up to 97 per cent" with the load table absent from its pages. A buyer comparing three families on "up to 97 per cent" is comparing three different definitions of up to.

The correction I owe my own premise

I began this reading with a thesis I expected to confirm: that Vertiv, like every other power vendor, prints the kilo-volt-ampere and the kilowatt on different pages and leaves the multiplication to the reader. The EXL S1 site planning data refutes it. kVA, kW, rectifier input current nominal and maximum, bypass and output current, battery discharge, AC-AC and DC-AC efficiency and full-load heat dissipation sit in one grid, per rating, for frames from 250 to 1,200 kVA. The join is printed, and it is printed better than most of the industry prints it.

What is not printed is the condition under which the joined numbers hold. The efficiency is defined at 1.0 power factor. The heat is that efficiency converted. The load band runs to 0.4 lagging. The temperature derating has no rate. So the gap moved: it is no longer between the electrical and the mechanical column of a data sheet, it is between the data sheet and the room. That is a smaller gap and a more expensive one, because a buyer who has learned to distrust kVA marketing will trust the BTU/h row, and the BTU/h row is the test bench.

The countercase deserves its own paragraph, because it is strong. Read as capability, nothing on these pages is deceptive. At unity power factor the frame delivers its nameplate kilowatts. The 0.7 leading to 0.4 lagging band is a real promise about a real inverter: it will hold its rated current into that load without derating itself. Measuring efficiency at 1.0 power factor is a published convention, defined before the numbers rather than after.

And the shift to unity output power factor across the family — 400/500 kVA beside 400/500 kW, 100-250 kVA/kW, 10/15/20/30/40 kVA at unity, 1500 VA / 1500 W, 2000/2000, 3000/3000, 6000/6000, 10000/10000 — is a genuine improvement in published information over the 0.9-rated frames it replaced. On a 0.9 frame a reader had to know the decimal to divide two columns. Here the decimal is one, printed, and equal.

What the customer still has to do himself

Four things, and a fifth if he is honest.

Size the output current on the kVA, because that is what the page prints and what the copper carries. 601 A on the 500 kVA frame at 480 V, and it does not fall when the load's power factor falls with it.

Size the cooling on the heat row, and check the row's perimeter. 61,876 BTU/h on the EXL S1 is the machine at unity. 18,645 BTU/h on the 100 kVA EXM includes a bypass cabinet and 29,253 BTU/h adds a transformer. Neither number tells the room what a 0.7 lagging load does to it, and no reviewed page does.

Ask the factory for the temperature derating rate, since two families announce a band between 40°C and 50°C and none prints a number inside it, and ask what the capacity is at your altitude and your ambient together rather than separately.

Ask which input power factor the nominal input current column was computed at, because the column reproduces at 1.0 while the same sheet prints 0.99 as its floor, and the generator upstream of the rectifier is sized on that number.

The fifth is the honest one: know your own load's power factor before you sign, because the vendor has told you a band and not a value, and at the bottom of that band a 500 kW frame is a 200 kW frame that still draws 601 amperes. That is what the kilo-volt-ampere buys, and it is worth what it costs. It is just not the number in the model name.

Documents read

All eleven were read on 26 November 2026. Two were retrieved as full page text with tables partly mangled by column extraction — the APM2 30-120 kW planning sheet, of which only the 120 kVA row was legible, and the APM2 data sheet, whose table alignment is unreliable — and no claim here rests on a cell whose alignment was in doubt. The GXT5 data sheet returned only its marketing lead paragraph; it contributed one sentence and no specification, and no rating in this article is attributed to it.

  • Liebert EXL S1 UPS 400-500 kVA/kW Data Sheet, SL-26097, R01/20 — link
  • Liebert EXL S1 UPS Guide Specifications 400-500 kVA 415 V 60 Hz, SL-70384_REV1_09-21 — link
  • Site Planning Data, Liebert EXL S1, SL-26092, 250-1200 kVA — link
  • Liebert APM2 Data Sheet, SL-71300 — link
  • Liebert APM2 30-120 kW, 400 V Site Planning Datasheet — link
  • Site Planning Data, Liebert EXM 3-Phase UPS 10-100 kVA/kW, SL-25645 — link
  • Liebert EXM2 Brochure 100 to 250 kW, UPS-EXM2-BR-V1-0126-EN — link
  • Liebert GXT5 UPS Data Sheet, SL-70719 — link
  • Liebert GXT5 UPS 1500-10000 VA 230 V Brochure, SL-70638, R10/22 — link
  • Liebert ITA2 10-40 kVA Data Sheet, MKA4L0UKITA2 Rev.4-07/2026 — link
  • Liebert EXM UPS 10-250 kVA/kW Brochure, SL-26003, R12/20 — link

Two disagreements are printed and neither is resolved here. The EXL S1 400 kVA frame at 100 per cent load reads 96.6 per cent in the guide specification and 96.5 per cent AC-AC in the site planning data; both are printed, the site plan is the document that also carries the heat, and the site plan's value is the one used in this article's closure. And the site planning file's name says 1000-1200 kVA while its table covers 250-1200 kVA; the revision is not printed in the captured text.

A distributor copy of the same table is reported to print 61,878 BTU/h where the reviewed address prints 61,876; the distributor copy is not among the eleven and is not adopted here.