Summary

  • Trane's CenTraVac catalogs are “selectable at an unmatched efficiency level of 0.45 kW/ton at standard AHRI conditions” — a sentence that names a condition and not a quantity, because the same phrase carries a full-load figure of 0.478 and a part-load figure of 0.296 in Trane's own 2020 brochure, and 0.45 is neither of them.
  • Of fourteen public documents read on 26 November 2026, exactly one page prints a chiller's capacity and its efficiency in the same row, and it states the rating conditions for a third number rather than for the two it prints together.

Two numbers that are one number

A ton of refrigeration is 12,000 British thermal units per hour. A kilowatt is 3,412 Btu per hour. Divide the first by the second and a ton of cooling is 3.517 kilowatts of cooling, which means COP is 3.517 divided by kilowatts per ton and kilowatts per ton is 3.517 divided by COP. Both operands are printed facts — twelve thousand, and the mechanical equivalent of heat — and no page in the fourteen documents I read on 26 November 2026 states the quotient as a constant.

Trane's own catalog prints it anyway, four times, without noticing. Its 2026 CenTraVac catalog gives typical heat-recovery efficiency as 0.64 to 0.84 kW/ton, “(5.49 to 4.18 COP),” against 0.54 to 0.57 kW/ton “(6.51 to 6.16 COP)” for a cooling-only machine (CTV-PRC021H-EN). Run the numbers: 3.517 ÷ 0.64 = 5.50 against a printed 5.49; 3.517 ÷ 0.84 = 4.19 against 4.18; 3.517 ÷ 0.54 = 6.51 against 6.51; 3.517 ÷ 0.57 = 6.17 against 6.16. Four pairs, two decimal places, the same constant each time, off by a hundredth because of rounding. Those four divisions are mine; the quantities are Trane's.

So the capacity and the virtue are the same measurement. A machine that delivers 830 tons and draws 0.837 kW/ton is drawing 695 kilowatts of electricity to deliver 2,919 kilowatts of cooling — 23.8 per cent, COP 4.20, both figures mine from Trane's two (Reference Design #506). A reader who does not perform that division sees a size and a scorecard and has no way to know they are the same axis.

What the 85 degrees is

The number that makes a capacity a capacity is the condenser water temperature, and the standard in force fixes it. ANSI/AHRI Standard 550/590-2023, approved 5 June 2023 and superseding the 2020 edition plus an addendum, prints in its Table 4 an all-cooling standard row of 54.00 °F entering and 44.00 °F leaving evaporator water, and 85.00 °F entering and 94.30 °F leaving water-cooled condenser water, with 95.00 °F dry-bulb for air-cooled machines (ANSI/AHRI 550/590-2023). Rating fouling is 0.000100 on the evaporator and 0.000250 on the tower, and zero on air-cooled and evaporatively cooled condensers.

And then the standard does something a reader will not expect. In the flow cells of that same row — the one field where a gallons-per-minute-per-ton figure could sit — Table 4 prints “Note - 8” and “Note - 9.” Those notes say rated water flow is determined by the water temperatures at rated capacity. The numeric flow range, 1.000 to 6.000 gpm per ton of refrigeration, appears only in Table 5, the application envelope, as a permitted span rather than a rating point. At the one place the primary document could have printed a number, it printed a pointer.

Trane's smaller water-cooled family makes the same move more openly. The Agility catalog states that “all selections are made using the Trane Select Assist (TSA) selection program,” that TSA “is certified by AHRI in accordance with AHRI Standards 550/590 (I-P) and 551/591 (SI),” that “changing the water flow rates may significantly alter the performance of a particular chiller,” and that flow limits “are included in the selection program” rather than the catalog (HDWA-PRC004E-EN). The rating is generated per selection, by software, for one configuration at a time. It is certified. It is also not a page a buyer can check against another buyer's page.

The average with four weights

The part-load number is a different object, and it is worth being exact about what it averages. AHRI 550/590-2023 Table 6 rates four points: 44.00 °F leaving chilled water at every load, condenser entering water of 85.00, 75.00, 65.00 and 65.00 °F at 100, 75, 50 and 25 per cent load, with fouling of 0.000100 and 0.000250, and flows held at full-load values at all part-load points. Equation 22a weights those four points 0.01, 0.42, 0.45 and 0.12 in the COP and EER form; Equation 22b inverts them for kilowatts per ton.

For non-standard condenser water the NPLV walks the entering water temperature down from the selected full-load value toward 65 °F by Equation 24, linear above 50 per cent load and flat at 65 °F below it.

Where those weights came from is documented, and Trane documented it. The 1999 Engineers Newsletter records the 1992 set at 17, 39, 33 and 11 per cent becoming 1, 42, 45 and 12 under the 1998 standard, which “changes the basis of that equation to 'more closely reflect actual operating experience found in the field for a single chiller'” (Engineers Newsletter 28-1). The same newsletter prints the rating conditions beside the weights: 3.0 gpm per ton on the condenser, 2.4 on the evaporator, 44 °F leaving chilled water, 0.00025 and 0.0001 fouling, flows constant — and a footnote allowing a manufacturer's higher minimum recommended entering condenser water temperature to be used in lieu of the specified value. The relief schedule went from a straight 85-to-60 °F line at 2.5 °F per ten per cent load to 85-to-65 at 4 °F between 100 and 50 per cent, flat at 65 below that.

Then the arithmetic that matters, and it is mine: those weights put 56 per cent of the year at 75 per cent load or above in 1992, and 43 per cent there in 1998, with 57 per cent at 50 per cent load or below. The 2009 ASHRAE Journal article reprinting Trane authorship states “57% of the operating hours of the chiller are at 50% load or less,” and that “only 1% of the chiller operation occurs at high loads and high condenser water temperatures” (A Closer Look at Chiller Ratings). Those two percentages are not independent measurements of how chillers run. They are the weights read back out of themselves. One per cent is the weight at the 85 °F, full-load point; fifty-seven is forty-five plus twelve.

That same article, quoting AHRI Appendix D, D2.1, states that the equation “was derived to provide a representation of the average part-load efficiency for a single chiller only” and is “not applicable for multiple chiller installations,” then adds that more than 90 per cent of central water-cooled chilled water plants are multiple-chiller installations, most commonly of two chillers. The standard's own metric describes the minority plant type.

A headline that names a condition instead of a quantity

Now the sentence. Both CenTraVac catalogs — the December 2024 printing and the November 2026 revision — carry the identical line: “It is selectable at an unmatched efficiency level of 0.45 kW/ton at standard AHRI conditions” (CTV-PRC021G-EN, CTV-PRC021H-EN). Neither labels 0.45 as full load or as part load.

Trane's own 2020 brochure shows why the label is not a formality. It prints “as low as 0.478 kW/ton full-load and 0.296 kW/ton IPLV at standard AHRI conditions” — one sentence, one condition phrase, two quantities (CTV-SLB036-EN). Divide: 0.478 ÷ 0.296 = 1.615, mine. The same words “at standard AHRI conditions” name two different measurements differing by a factor of 1.6. The unlabelled 0.45 matches neither: it is 6.2 per cent below the 2020 full-load figure and 52 per cent above the 2020 part-load figure, in kilowatts per ton, both quotients mine. Read as full load it is a small regression; read as a part-load value it is a large one. No reviewed page says which, and that comparison spans a family sold from 120 to 4,000-plus tons across more than one refrigerant — it is not one machine against itself.

The brochure prints a third number too, in a separate environmental passage: “if every chiller could operate at CenTraVac's 0.45 kW/ton efficiency.” Three figures for one family, two labels, one condition phrase.

The regional product page adds the family ranges without any rating basis at all. CenTraVac CTV is listed at 125 to 2,000 tons with IPLV 0.32 to 0.43 kW/ton and full load 0.50 to 0.70; CDH duplex at 1,400 to 3,950 tons with 0.30 to 0.52 and 0.49 to 0.58; RTWD 80 to 250 tons at 0.48 to 0.57 and 0.62 to 0.75; RTHD 125 to 430 at 0.37 to 0.56 and 0.57 to 0.71; HDW 150 to 450 at 0.31 to 0.35 and 0.52 to 0.65; CVHS 180 to 380 at 0.28 to 0.32 and 0.48 to 0.55 (CenTraVac product page, Latin America). That table prints no COP, no entering condenser water temperature, no leaving chilled water temperature, no flow, no fouling and no rating-condition statement for any row. And the CTV full-load floor of 0.50 sits above the catalog's own 0.45 headline.

The one page that puts them in a row

Here is the count that took fourteen documents to establish. Exactly one page prints a capacity and an efficiency in the same row: Reference Design #506, dated 1 September 2026, describing a 250-megawatt AI factory on air-cooled Ascend ACR chillers. Its per-chiller table reads “Reduced | 0.757 kW/Ton 712 Tons” and “Max | 0.837 kW/Ton 830 Tons” (Reference Design #506).

The page then states its rating conditions, and this is the whole article in one footnote: “Capacity is based on the nominal unit at 550 tons at these conditions: 30°C (86°F) supply water at a 40°C (104°F) ambient condition.” A third tonnage, a third set of conditions, printed for the nominal figure — and nothing for the 0.757 or the 0.837. The same section also states without reconciliation that “the capacity of the unit in this design is 550 nominal tons” beside 712 and 830, and I adopt neither as the definition of the other.

The rest of that table divides cleanly, which is how I know the megawatt in it is cooling and not electricity: 2,500 kW ÷ 712 tons = 3.512, and 2,250 kW ÷ 640 tons = 3.516, both mine, both landing on the constant.

Per-chiller load is 2.5 MW (712 tons) on the high-temperature direct-to-chip loop and 2.25 MW (640 tons) on the medium-temperature airside loop, at 2,131 LPM (563 GPM) and 3,245 LPM (857 GPM); facility supply is 22 °C airside and up to 30 °C on the high-temperature loop, blended with a 47 °C return to reach 37 °C at the CDU; design maximum ambient is 40 °C in Chicago against an operating range of −40 to 63 °C; restart after power loss is 160 seconds at 80 per cent load; PUE improves from 1.201 to 1.083 with integrated free cooling, about a 49 per cent reduction in annual cooling energy.

So the data-centre document, written for the densest cooling load anyone currently builds, reproduces the defect it inherits. It puts the two numbers in one row and leaves the condition they are rated at to be inferred from a footnote about a different number.

The thirteen questions

A rated capacity is a promise made at a temperature, and the temperature is the seller's to choose. The test is a named list, not an argument. For any chiller on offer, ask:

  1. Which page prints the capacity in tons?
  2. Which page prints the entering condenser water and leaving chilled water temperatures at which those tons hold?
  3. Which page prints the cooling in kilowatts, and does it divide to 3.517 kilowatts per ton?
  4. Which page prints the efficiency in kilowatts per ton?
  5. Which page prints COP?
  6. Which page prints both, with the conversion applied?
  7. Which page prints full-load efficiency?
  8. Which page prints a part-load value?
  9. Which page labels that part-load value with its load points and its weights?
  10. Which page prints the part-load table itself, so a reader can recompute the weighted average?
  11. Which page prints the fouling allowance, the evaporator flow and the minimum load — and what the machine does below that minimum?
  12. Which page corrects capacity for the condenser temperature a summer roof actually delivers?
  13. Which single page prints tons and kilowatts per ton at the buyer's own water temperatures and flows?

In this read, question 1 is answered on several pages and question 13 only by a page that answers question 2 for something else. Questions 11 and 12 have partial answers: the standard's Table 5 gives an application envelope for fouling and flow, and Trane's modelling help documents a cubic curve that “correlates the chiller's evaporator capacity as a function of the condenser entering water temperature,” used “to correct nominal capacity at off-design condensing temperatures” (TRACE 3D Plus, Curve tab). The correction exists. It lives in software.

Countercases, printed against my own premise

I reserved this subject with a thesis and said I would test it honestly rather than assume it. Seven printed facts push back.

A capacity-correction table is not absent. It appears in Trane's rental catalog, which arrays capacity in tons across condenser entering water at 70, 75, 80, 85, 90 and 95 °F and leaving water at 60, 55, 50, 45 and 40 °F, with an example table assuming 540 gpm evaporator and 675 gpm condenser flow (TEMP-PRC009B-EN). The derating is disclosed. What that table carries is capacity only — no full-load kW/ton, no IPLV, no COP, no fouling. The correction exists for the number a buyer uses to size a pipe and not for the number he uses to choose a machine.

Trane's modelling software corrects in the open, and the 2024 catalog prints a kW/ton-against-load figure for one 800-ton machine at 42 °F and 55 °F evaporator, 85 °F entering condenser water and 2.5 gpm per ton, with curves at 85, 75 and 65 °F entering condenser water. The shape is visible. What a reader cannot do with a three-curve figure is recompute a four-point weighted average at four named condenser temperatures.

The part-load assumption is filed in the open, and the manufacturer built the remedy: myPLV, which Trane describes as adjusting for climate zone, building type, plant size, number of chillers, tower control strategy and other factors, buildable from “a user-entered system load profile,” returning “suitable test conditions that represent common operating points for that chiller once installed” (Comprehensive Chilled-Water System Design). The buyer's load shape is available — per selection, on request, from the manufacturer's tool, not as a published number a reader can check.

And one page does put capacity and efficiency in one row. It is Reference Design #506, and it is also the page that states rating conditions only for its 550 nominal-ton footnoted figure. The countercase and the finding are the same document.

Where the averaged number becomes money

Two municipal and utility programmes turn all of this into a cheque, and they do not agree on the threshold.

Austin Utilities' 2026 commercial and industrial chiller rebate splits equipment into Path A, “Water and Air Cooled Chillers with Fixed Speed / No Demand Limiting Controls,” and Path B, “Water and Air Cooled Chillers with Variable Speed / Demand Limiting Controls” (Austin Utilities 2026 rebate schedule). Path A pays a flat $15 per ton for water-cooled and $8 for air-cooled with no efficiency term at all. Path B pays $15 plus $200 × (minimum IPLV − rated IPLV) per ton for water-cooled, and the footnote prices the same bonus “for each 0.01 kW per ton below the Minimum IPLV Efficiency.” Those are one rate in two units: $200 × 0.01 = $2.00, mine. A machine 0.10 kW/ton better than its band's minimum earns $20 per ton over the $15 base, so 600 tons earns $21,000 where the same machine at the threshold earns $9,000 — again my multiplication over their printed rates.

Public Service Company of Oklahoma's chiller summary asks a different question in almost the same words, demanding “Cooling Capacity (tons @ AHRI conditions),” “AHRI Full Load Efficiency (kW/ton or EER)” and “IPLV (@ AHRI conditions, kW/ton or EER)” for both the existing and the proposed machine (PSO Chiller Project Summary v25). It prints no rebate dollar amount, so I quote none.

Now put the two schedules side by side at the same AHRI conditions. At 300 to under 600 tons, water-cooled centrifugal: Austin Path A requires 0.560 full load and 0.520 IPLV; PSO Path A requires 0.576 and 0.549, which is 0.016 kW/ton looser at full load and 0.029 looser on IPLV, my subtractions. At 600 tons and above: Austin 0.560 and 0.500 against PSO 0.570 and 0.539, 0.010 and 0.039 looser. A machine at 0.565 kW/ton full load with a 0.535 IPLV is paid in Oklahoma and refused in Minnesota, at identical AHRI conditions, because each programme set its own baseline instead of restating the standard.

Neither threshold is an AHRI or ASHRAE minimum; both are choices.

What the average costs when your load does not move

The consequence is arithmetic, so here is arithmetic with the operands named and the illustration labelled as mine. Take a machine reading 0.5 kW/ton at 100 per cent load and 85 °F, 0.4 at 75 per cent and 75 °F, 0.35 at 50 per cent and 65 °F, 0.35 at 25 per cent and 65 °F. Its published part-load value is 1 ÷ (0.01/0.5 + 0.42/0.4 + 0.45/0.35 + 0.12/0.35) = 1 ÷ 2.699 = 0.371. Under the 1992 weights the same four points give 0.389.

A data hall that holds near 100 per cent load sits at the 85 °F point and runs at 0.5 kW/ton while the printed number is 0.371, and the point it actually occupies carries one per cent of the weight. The gap is 0.129 kW/ton, 35 per cent of the printed figure.

That is not a claim about Trane's chillers. It is a claim about what a weighted average is: a statement about a load shape, printed as though it were a property of a machine. Buy tons at a rated condition and the shortfall on the design day arrives as a supply-water temperature you cannot hold, not as a number anyone printed. Compare two machines on part-load efficiency and you compare two averages, which can invert on a flat load. Pay a rebate on a kW/ton threshold and you pay on a load shape the recipient may not have.

What this reading does not establish

Every absence here is a count over fourteen distinct public documents read on 26 November 2026, listed with their URLs, and not a claim that a figure is unpublished anywhere.

The text came through a routed search layer rather than page-by-page inspection, and equation typography and table-cell alignment are imperfect in several documents. The CenTraVac Performance Data pages 48 to 52 in imperial units and page 70 in SI did not render at all, so no per-model row from either catalog is claimed here — including the question of whether one row prints tons, full-load kW/ton, part-load value and COP together. That question is open.

The November 2026 catalog revision carries a printed date later than the read date and I cannot confirm whether it is published or pre-released; it is cited only as a second printing of a sentence that also appears in the 2024 revision. Reference Design #506 prints 550 nominal tons and 712 and 830 tons in one section and reconciles them nowhere, and the packet adopts neither. No reviewed page labels the 0.45 kW/ton headline as full load or part load.

No reviewed page prints a minimum-load percentage for any named CenTraVac model; the standard handles a machine that cannot unload to 25, 50 or 75 per cent by interpolation and a degradation procedure rather than by stating one number. The Austin form exists at two paths, one with duplicated or misordered rows, and the values here follow the cleaner extraction; its air-cooled EER figures are reproduced to the thousandth as printed. PSO prints no rebate rate, so none is quoted. Two utility programmes are two printed schedules and not a sample of an industry.

The thirteen questions, the load-shape arithmetic and the consequences are BTW's own reasoning over printed evidence, and are written as such rather than attributed to any source.