Summary

  • One Landis+Gyr data sheet prints two starting currents for the same meter, 0.01 A under the European class B label and 0.005 A under the IEC class 0.5 S label, while both ladders agree exactly at the minimum current and at the rung where the accuracy class begins.
  • Behind a 100/5 current transformer the two starting currents become 0.2 A and 0.1 A of primary current, 138 W and 69 W across three phases at 230 V, and the transformer's own class holds only from 20 A of its 100 A rating — four times above the meter's.

The only rung that disagrees is the one that decides whether you count

Take the technical data for the E570 Series 2, a transformer-connected three-phase meter published by Landis+Gyr on 20 September 2018 (E570 Series 2, D000063744 en c). For European class indexes B and C it prints rated current 1.0 A or 5.0 A, minimum current 0.01 A or 0.05 A, transitional current 0.05 A or 0.25 A, maximum current 2.0 A or 10.0 A, and a starting current of 0.002 A or 0.01 A for class B and 0.001 A or 0.005 A for class C. On the IEC side of the same sheet the instrument is class 0.5 S to IEC 62053-22 as a ZxY405 or class 1 to IEC 62053-21 as a ZxY410, with maximum current at 200 per cent of rated current, a thermal current of 12 A, and a starting current of 0.1 per cent of rated current (typical 0.07 per cent) for the 0.5 S variant and 0.2 per cent (typical 0.14 per cent) for the class 1 variant.

Set the sheet at its 5 A rating and the two vocabularies line up rung for rung, except at the bottom. Both ladders give a minimum current of 0.05 A. Both put the beginning of full accuracy at 0.25 A, which is what a transitional current means: the current at and above which, up to the maximum, the full accuracy requirement applies (EN 50470-3:2022). Both give a maximum of 10 A. The starting current is where they part: 0.01 A on the European label and 0.005 A on the IEC label, a factor of two, in one table, for one piece of hardware.

That is the interesting rung. A minimum current defines where the mandated error band begins, and a transitional current defines where the full accuracy band begins. The starting current defines something earlier and blunter: the load below which the instrument is permitted to register nothing at all.

Two labels that agree on the floor of the warrant and disagree on the floor of the permission mean that the answer to "at what size of load does my consumption begin to exist" depends on which of the meter's two identities the reader was handed — and both identities are printed on the same page by the same manufacturer, each truthful in its own vocabulary.

Three of the four cells sit on the standard's own ceiling

It is tempting to read a precise figure like 0.01 A as engineering caution. Compare it with the bounds the European standard actually permits and the caution disappears.

For transformer-operated class B meters, EN 50470-3 gives a starting current of at most 0.04 times the transitional current, a minimum current of at most 0.2 times the transitional current, a nominal current of exactly 20 times the transitional current, and a maximum of at least 24 times it (EN 50470-3:2022, Tables 2 and 3). Against those bounds the E570's 5 A cells read as follows, and the division is mine: 0.01 A divided by 0.25 A is 0.04, precisely the permitted starting-current ceiling; 0.05 A divided by 0.25 A is 0.2, precisely the permitted minimum-current ceiling; 5 A divided by 0.25 A is 20, the prescribed nominal-to-transitional relation; 10 A divided by 0.25 A is 40, above the required 24. The 1.0 A variant repeats the first two: 0.002 A over 0.05 A is 0.04, and 0.01 A over 0.05 A is 0.2.

Three of the four cells are not conservative at all. They are the loosest values the class allows, arrived at exactly. A class B meter that starts sooner than 0.01 A exists in principle and is not represented by this sheet; a class B meter that starts later does not, because the standard stops it there. When a specification is written from this document, the starting current it inherits is the worst permitted case of its class, not the best available.

What the sheet leaves to the standards it names

Neither the E570 sheet nor the E650 Series 4 sheet reproduces a percentage-error table. Both refer accuracy to the European and IEC standards and stop there, and both print their own power consumption as typical values with no maximum (E650 Series 4, D000062002 en a). The reader who wants the error at 0.06 A has to leave the product document and open the standard, which is exactly the journey that separates a purchase decision from a specification.

What the sheets do print is burden, and the E650 prints it better than most: per phase in the current circuit, 5 mW and 5 mVA at 1 A, 0.125 W and 0.125 VA at 5 A, 0.5 W and 0.5 VA at 10 A; per phase in the voltage circuit, 0.4 W and 0.7 VA at 58/100 V, 0.5 W and 1.0 VA at 110/190 V, and 0.7 W and 1.7 VA at 220/380 V without a communication unit.

The same instrument therefore carries a stated active burden and a stated apparent burden, and the relation between them is not constant: 0.4 over 0.7 is 0.571, 0.5 over 1.0 is 0.500, 0.7 over 1.7 is 0.412, all mine, each quotient taken inside one printed row. The higher the voltage, the more of the meter's own consumption is real power rather than reactive. Three phases of that voltage-circuit burden at 220/380 V come to 2.1 W of active power, my multiplication.

Multiply the ladder by twenty

A transformer-operated meter is never bought alone. Put a 100/5 current transformer in front of it and every rung of the ladder is multiplied by twenty, which is my quotient from the ratio lists printed by the manufacturers below.

On the IEC 0.5 S label the starting current of 0.1 per cent of 5 A, or 0.005 A in the secondary circuit, is 0.1 A of primary current. The minimum current of 0.01 times rated current is 0.05 A secondary and 1 A primary. The point where the plus-or-minus 0.5 per cent limit begins, 0.05 times rated current, is 0.25 A secondary and 5 A primary. The maximum of 200 per cent of rated current is 10 A secondary and 200 A primary (IEC 62053-22:2020, E570). On the European class B label the same four rungs are 0.2 A, 1 A, 5 A and 200 A of primary current. The ladders disagree at the first rung and coincide at the other three.

Convert to watts, stating the assumptions: 230 V phase to neutral, unity power factor, and the products are mine. One phase at 0.1 A is 23 W, so three phases are 69 W. At 0.2 A it is 46 W on one phase and 138 W across three. At 1 A, 230 W and 690 W. At 5 A, 1,150 W and 3,450 W. At 200 A, 46,000 W and 138,000 W.

Those watts are the piece. A building wired through a 100/5 transformer whose meter carries the IEC label is permitted to see nothing below roughly 69 W of three-phase load at unity power factor, and a building whose meter carries the European label is permitted to see nothing below roughly 138 W. Above that and below 3,450 W the instrument registers and its class does not warrant the registration. Above 3,450 W both ladders are satisfied.

The transformer has a higher floor than the meter

The chain has three floors, and the meter's is not the highest.

The measuring current transformer's own accuracy class holds only above a stated fraction of its rated primary current. IEC 61869-2 puts the ratio-error and phase-displacement limits of classes 0.1 to 1 from 5 per cent of rated primary current and adds a 1 per cent column for classes 0.2 S and 0.5 S (IEC 61869-2:2012). A secondary rendering of the same tables gives the comparison plainly: a class 0.5 transformer has no specified ratio-error limit at 1 per cent of rated primary current and plus or minus 1.5 per cent at 5 per cent, while a class 0.5 S transformer is limited to plus or minus 1.5 per cent at 1 per cent and plus or minus 0.75 per cent at 5 per cent, and both reach plus or minus 0.5 per cent only from 20 per cent upward (Tiza Group, class 0.2 S and 0.5 S extended range).

On a 100 A rated primary current, 20 per cent is 20 A of primary current, which at 230 V and unity power factor is 4,600 W on one phase, my arithmetic. The meter's full-accuracy rung behind the same transformer is 5 A of primary current, 1,150 W on one phase. The transformer's class floor is four times higher than the meter's. Between 1,150 W and 4,600 W the meter is inside its class and the transformer that feeds it is not: the scales are matched to each other at the top of the range and mismatched at the bottom, and the mismatch is invisible on either document taken alone.

The class designation, not the transformer as a category, decides which of those two sentences applies. Four named manufacturers print the choice explicitly. VTEKE's BK series covers 5 A to 200 A primary with 5 A secondary in classes 0.5 S, 0.5 and 1.0, rated power up to 15 VA, with ordering blocks labelled burden 5 VA and burden 10 VA and a printed surge current limitation factor of 5 (VTEKE BK series). LUMEL's catalogue gives, for one type, 100 A as 1 VA in class 0.5 S against 1.5 VA in class 0.5, and 200 A as 5 VA in both, with rated burdens from 1 VA to 100 VA and instrument security factors of 2.5, 5 and 10 (LUMEL current transformers). Crompton lists 5 A secondary as standard with 1 A on request, burdens from 1 VA to 100 VA, classes 0.5, 1 and 3 with 0.2, 0.2 S and 0.5 S optional, and security factors of 5, 10 and 15 (Crompton Instruments). CIRCUTOR's TD5 200/5 A sheet prints class 0.5 at 2.5 VA, class 1 at 3.75 VA and class 3 at 5 VA with a safety factor of 5, and its range table gives the 100/5 A version of class 0.5 at 1.5 VA (CIRCUTOR TD5).

So the rated burden is not a property of transformers. It is a property of one ratio in one class from one catalogue, printed per row, and the two catalogues above disagree about the same 100 A ratio by a factor of more than three because they describe different product ranges. A buyer who orders "a 100/5 class 0.5" has specified a ratio, a class and nothing else. The 1 VA or the 1.5 VA or the 5 VA, the security factor and the secondary current are separate printed choices, and the meter's own current-circuit burden of 0.125 VA at 5 A is an eighth of a 1 VA transformer's rated output, my division.

The chain has a budget and the budget is printed on four documents.

One band where the sources disagree, stated as a disagreement

The class 0.5 S error table contains a band that decides how much of the light-load range is warranted. The IEC text itself could not settle it here, because the preview of the 2020 edition stops before page 12, where Table 3 sits (IEC 62053-22:2020). Two national instruments reproduce it. The Saudi adoption of the 2016 edition gives class 0.5 S as plus or minus 1.0 per cent from 0.01 to 0.05 times rated current at power factor 1, plus or minus 0.5 per cent from 0.05 times rated current to maximum at power factor 1, plus or minus 1.0 per cent from 0.02 to 0.1 times rated current at 0.5 inductive and 0.8 capacitive, and plus or minus 0.6 per cent from 0.1 times rated current upward (SASO IEC 62053-22:2019). The Croatian official gazette instrument of 30 January 2006 gives the same numbers for the same bands (Narodne novine, NN 11/2006). A secondary standards catalogue prints plus or minus 0.6 per cent for the 0.02 to 0.1 band, not 1.0 (plusstd catalogue page).

Two national instruments against one catalogue page is not a close call, and the article uses 1.0 per cent for that band while recording that the 2020 text itself was not read at that page. The practical size of the disagreement is 0.4 percentage points across a band that runs from 2 to 10 per cent of rated current — which is to say, in the range where a lightly loaded building actually sits. Anyone quoting a class 0.5 S tolerance at 5 per cent of rated current on the inductive side is quoting one of two published answers.

Nineteen documents, no conversion

Nineteen documents were read for this piece, and the count is over the documents read, not a claim about what exists. Not one of them converts a starting current, a minimum current, a transitional current or a maximum current into watts at a stated voltage and power factor, and not one of them, for a named meter and a named transformer ratio, states the load below which the printed class guarantees nothing.

The standards are specific about currents and silent about loads. IEC 62053-21 gives starting current as 0.004 times rated current for direct-connected classes 0.5 and 1 and 0.005 for class 2, and 0.002 and 0.003 through current transformers, with minimum current at 0.05 direct and 0.02 through transformers (IEC 62053-21:2020). IEC 62053-22 gives 0.001 times rated current as the starting current for every S class and 0.01 as the minimum, then explains in a note that the standard CT measuring range runs from 0.05 times rated current for classes 0.1 to 1 while the special range runs from 0.01 for classes 0.2 S and 0.5 S. IEC 62053-24 carries the same split into reactive energy, with 0.001 times rated current for class 0.5 S against 0.002 for class 1 S through transformers (IEC 62053-24:2020) — so on one meter declaring active class 0.5 S and reactive class 1 S, the reactive reading begins at twice the current of the active one, and a power factor computed from the two at light load compares an instrument with itself at two different floors.

The parent document defines the vocabulary and leaves the numerals to a table the preview did not expose. IEC 62052-11 sets out nominal, starting, minimum and maximum current and the current ranges in clauses 4.2.1 to 4.2.5, power consumption in 4.4, and a maximum power consumption table on page 38 (IEC 62052-11:2020). Secondary commentary supplies the widely quoted ceilings behind that table: 2 W and 10 VA per phase in the voltage circuit at nominal voltage, and 1 VA per phase in the current circuit for static meters, against 4 VA for an electromechanical class 1 instrument (CLOU GLOBAL, meter power consumption). The same source makes the point that matters for a specification: the current-circuit figure is anchored to nominal current and the loss rises with the square of current, so a burden quoted in VA is not a burden at every load (CLOU GLOBAL, self-consumption in the current circuit). The E570 confirms the shape without saying so — 0.125 VA at 5 A against 0.005 VA at 1 A is 25 for a fivefold current change, which is five squared, my division.

One direct-connected sheet completes the picture of what the manufacturer does and does not do. The E450 Series 4 prints base current 5 A, maximum current 100 A, class 1 or 2 to IEC 62052-11 and 62053-21 with a starting current of 0.4 per cent of base current, and on the European side reference current 5 A, minimum current 0.25 A, maximum 100 A, class B or A, starting current 0.4 per cent of reference current with a cap of 20 mA (E450 Series 4, D000053825 en k). That starting current is 0.02 A. At 230 V and unity power factor it is 4.6 W on one phase, my multiplication; the European minimum current of 0.25 A is 57.5 W, and the ratio between the two rungs is 12.5. The same document states total meter power consumption below 2.5 W active and below 8.5 VA apparent, whole meter, not per phase, so it cannot be set beside the transformer-operated sheets' per-phase figures without saying which basis is in use.

The instrument is also a load

The E450's whole-meter active burden of under 2.5 W is 54 per cent of the 4.6 W its own starting current represents at 230 V and unity power factor, my arithmetic on two cells printed in one document. The meter is entitled to draw more than half of the smallest load it is obliged to notice — which would be a curiosity if any of the nineteen documents said whether the meter's own consumption is inside or outside the quantity it registers. None does. It is one of the open surfaces this reading leaves behind.

What a reader can recompute at the kitchen table

Four numbers, each from printed cells and each labelled mine. A class 2 meter connected directly begins to register at 0.005 times its rated current and its class holds from 0.05 times rated current, so between those two rungs it counts something it does not warrant, and the ratio is ten. Behind a 100/5 transformer, a class 0.5 S meter begins at 0.1 A of primary current and warrants from 5 A, and the ratio is fifty.

A class 0.5 transformer holds its plus or minus 0.5 per cent from 20 per cent of rated primary current, which on a 100 A rating is 20 A and on a 200 A rating is 40 A, so its floor moves when the ratio changes and the meter's does not. And 0.4 per cent of 5 A is 0.02 A, one hundredth of the current at which the same meter's European minimum sits.

A building operator can run those four lines against a base-load reading from his own switchgear and learn something the utility bill does not tell him: how much of his quiet-hours consumption is being counted by an instrument whose class applies, and how much is being counted by an instrument whose class does not. The gap is largest exactly where consumption is smallest, and quiet hours are where consumption is smallest.

Where this leaves the number on the bill

The bill does not print a class. It prints a quantity. The quantity was registered above a floor that the meter's own document states in amperes, multiplied by a ratio the transformer's own document states, with a class that begins at a third figure in a fourth document that the meter's sheet names and does not reproduce. Every one of those figures is truthful. The chain is the finding, not any single link: two floors, a ceiling, and a set of units that no reviewed page joins.

The consequence for the numbers this publication has already priced is direct. A power usage effectiveness is a quotient of two energies whose meters each have a starting current; a demand charge is computed on a register that integrates above a floor; a per-megawatt-hour rate multiplies a quantity that a class warrants only above a stated current. None of those figures is wrong. Each is a figure with a lower bound that the person dividing it has not read, and the bound is printed — in amperes, on one page, twice.

Reading limits

All nineteen documents were read through a search index rather than opened page by page, so pagination and any omitted tables remain unverified. The IEC 62053-22 preview stops before page 12, so its class 0.5 S percentage cells come from a Saudi adoption of the 2016 edition and a Croatian instrument reproducing the 2003 edition, against one secondary catalogue page that disagrees in one band. The EN 50470-3 error rows were reordered by the PDF parser; the numerals are legible and the row alignment should be checked against a printed copy. The IEC 62052-11 preview exposed only front matter, so the 2 W, 10 VA and 1 VA maxima are secondary.

The Landis+Gyr sheets print typical burden only, with no maximum, and reproduce no percentage-error table. The E450 burden is whole-meter rather than per phase. The IEC 61869-2 column alignment is unreliable in the extracted text, so no cell was taken from it directly, and the 1, 5 and 20 per cent points come with the secondary rendering named beside them.