Summary
- Digital Realty’s release prints 6.4 MW for NBO2 under the single word “capacity”. The company’s own specification page prints no megawatt at all, and a 2024 company release called the same building “IT load of 6.5 MW”, expected online in the third quarter of 2025.
- Kenya’s approved tariff bills industrial customers in shillings per kVA of demand and per kWh, by voltage level; the regulator’s statistics report for the year to 30 June 2026 counts five customer categories and no data centre at all.
What the release prints
The 7 September 2026 announcement opens with the figure and no noun for it: “Digital Realty … today announced the opening of the 6.4-megawatt (MW) Nairobi Two Data Center (NBO2).” The subheadline is where the number acquires a label: “NBO2 adds 6.4 MW of capacity to Digital Realty’s Nairobi campus as iColo transitions to the Digital Realty brand in Kenya and Mozambique.” Capacity — not critical load, not IT load, not installed, not contracted. The company’s investor-relations copy carries the same two sentences, and so does the Kenyan repost dated 07/09/26.
One page later, the number is gone. NBO2’s specification page prints a total building size of 12,000 ft² (1,100 m²), UPS redundancy of 2N and cooling redundancy of N+2 — and, in the text I read, no megawatt, no kVA, no power field of any kind.
One building, three labels, two figures
The same building has older paperwork. A 2024 iColo release about solar panels says: “The company’s second data center in Nairobi, NBO2, with an IT load of 6.5 MW, is expected to come online in Q3 2025.” IT load. 6.5. Expected. The 2026 announcement neither repeats the label nor corrects the number; the two documents differ by 0.1 MW and by everything else.
Downstream the label drifts further. A Construction Review Online factsheet prints “Total IT Power Capacity: 6.4 Megawatts (MW)” — the clearest case in this set of a third party supplying a measurement point the company never printed, so the label belongs to the outlet. DataCenterDynamics stays with “6.4MW of capacity”, gives the same 12,000 sq ft, and adds the campus history: NBO1 opened in September 2019 in Karen with 624 sqm, and 450kW of solar went in at NBO1 in 2024. CIO Africa places NBO2 in Karen about 300 metres from NBO1 and reports the country manager, Wanja Muriithi, citing high-density capacity and a renewable-heavy grid — an outlet reporting remarks, which is not the same thing as release text.
The company’s own house vocabulary is the most useful document in the set. The iColo homepage states “iColo is now Digital Realty” and then labels its African sites: Maputo One “IT Power: 0.2 MW”, Mombasa One “IT Power: 0.9 MW”, Mombasa Two “IT Load: 1.75MW”. Two labels for one quantity, on one page, with no note distinguishing them. The EMEA locations page goes the other way: Nairobi appears as two facilities of 27,500 ft² (about 2,550 m²), “leading connectivity hub in East and Central Africa”, and no megawatt for the market at all. Those 2,550 square metres do not reconcile with 624 plus 1,100, so the market total is quoted as a market total and nothing more.
Three labels, two figures, one building. The 0.1 MW is not the story. The story is that no document in this set says where on the electrical chain the 6.4 MW is taken, over what interval, or whether it describes the plant as designed or as running.
What the meter asks for
The buyer’s side is more precise than the seller’s and, for this question, less useful than it looks. Kenya Power’s industrial customer is defined by voltage. EPRA’s statistics report reproduces the approved 2025/26 base tariffs: KSh 13.44 per kWh at 415 V, 12.16 at 11 kV, 11.68 at 33 kV, 11.42 at 66 kV, 11.16 at 132 kV and 10.00 at 220 kV, with demand charges of KSh 1,100, 700, 370, 300, 300 and 200 per kVA at the same levels.
The Gazette notice behind the schedule — No. 3899 of 24 March 2023, made under section 11 of the Energy Act 2019, effective 1 April 2023 — is where the definitions live. CI1 is 415 V three-phase four-wire above 15,000 units in a post-paid billing period; CI2 to CI6 sit at 11, 33, 66, 132 and 220 kV; CI7 covers Special Economic Zones. The demand charge is expressed per kVA, not per kW. Off-peak runs weekdays 22:00–06:00, Saturdays and holidays 00:00–08:00 and 14:00–00:00, Sundays all day, and the time-of-use discount applies only to units above a monthly threshold set at a six-month average plus 6 per cent for existing customers, three months plus 6 per cent for new CI1 to CI7 customers.
In the copy I read, the schedule prints no demand averaging interval — no fifteen minutes, no thirty. A demand charge without a stated window is still a demand charge, but the window is what makes two demands comparable, and it is the first field a facility engineer asks about.
The tariff’s own clock is also unset. EPRA’s notice of 5 June 2026 records that Kenya Power’s retail tariff review application of 31 March 2026 was withdrawn, and does not say what applies after 30 June 2026. Kenya Power’s abridged application states that the Fourth Tariff Control Period runs from 1 April 2023 to 30 June 2026 and that the proposed Fifth would run from 1 July 2026 to 30 June 2029, with proposed 2026/27 CI-1 rates of KSh 15.80 per kWh and KSh 1,100 per kVA. Those are proposals. The regulator’s September 2026 report still tabulates the 2025/26 rates, which is why I treat those as the ones in force.
Classification is by voltage and volume, not by industry, so nothing in the schedule places a data centre anywhere. The one reviewed page that does is a commercial Nairobi development guide: “Data centres operating as high-voltage industrial consumers are categorized under Commercial/Industrial tariffs (CI1 to CI5).” Its CI5 rate of KES 13.90 per kWh conflicts with EPRA’s KES 11.16, and it lists no CI6 or CI7, so the class is the guide’s claim rather than the regulator’s.
What the state counts
EPRA’s report puts total installed generation capacity at 3,987.20 MW as at 30 June 2026 — 3,263.02 MW interconnected, 676.60 MW captive, 47.58 MW off-grid, which add to the total — and peak demand at 2,514.28 MW on 29 June 2026, 8.55 per cent above the 2,316.22 MW peak of 2024/25.
Consumption was 12,444.71 GWh. Large commercial and industrial took 5,920.06 GWh, or 47.57 per cent; domestic 4,327.07 GWh, 34.77 per cent; small commercial 2,012.17 GWh, 16.17 per cent; street lighting 173.17 GWh, 1.39 per cent; e-mobility 12.25 GWh, 0.10 per cent. (The percentage re-derives from the two consumption figures; that check is mine.)
Five categories. No data centre. If the industry appears in this table at all, it is inside “large commercial and industrial”, beside the cement plants, the hotels with industrial kitchens and the shopping malls. That is the asymmetry worth printing: the same report can date its system peak to a single day and carry installed capacity to two decimal places, and it cannot state what its newest class of electrical load draws.
The 82 per cent
The 2024 release also says Kenya’s grid is 82 per cent renewable, citing EPRA. Follow that sentence back. Kenya’s National Energy Compact 2025–2030 says renewables “now accounts for 82% of the country’s total installed electricity generation capacity and 93% of actual energy consumption”, and elsewhere in the same document uses 83 per cent for clean installed generation. So 82 per cent is a share of installed capacity, on a 2024 baseline, in a document that prints two numbers for one idea.
EPRA’s biannual report for the financial year reads differently: 78.79 per cent of the energy supplied to the national grid in July–December 2025 came from renewable sources; renewable installed capacity was 2,957 MW, or 80.60 per cent of the total at December 2025; thermal supplied 9.11 per cent of energy and imports 12.10 per cent. None of those is 82 per cent, and none of them is a share of what any Nairobi rack consumed on any day in 2026.
The solar detail repeats the pattern. The 2024 release claims more than 450 kW within the NBO campus and more than 650 kW across the Nairobi and Mombasa campuses; DataCenterDynamics attributes 450 kW to NBO1 in 2024. Both readings are printed here and neither is adopted. That release also projects “20+ MW consumption at full capacity” for the campus — the only campus-level power figure I found, and a master-plan statement from 2024 rather than a 2026 measurement.
My arithmetic, and where it stops
At the 11 kV demand charge of KSh 700 per kVA, 6.4 MW read as 6,400 kVA would attract KSh 4,480,000 a month in demand charges. That assumes a power factor of 1.0, and no document in this set prints a power factor; the arithmetic is mine and it is not a bill.
6.4 divided by 2,514.28 is 0.25 per cent of national peak demand. I print it to refuse it: a coincident system peak is not a customer’s billing demand, and the quotient measures nothing a planner can use.
6,400 kW divided by 1,100 m² is about 5.8 kW per square metre. Refused as a density, because one term is a building size and the other an undefined label.
450 kW divided by 6,400 kW is 7 per cent. Refused too: a campus numerator over a building denominator, two years apart.
Who supplies the missing specification
The plant is not in question. NBO2 opened alongside NBO1 on a campus the company says reaches more than 100 networks, two internet exchange points and a satellite teleport, and the interconnection case for Nairobi does not depend on this article.
What is unfinished is the record of what the building draws. The seller supplies the missing specification, and the seller who supplies the specification defines the resource. A regulator that wanted to plan against data-centre load would have to ask the operator for the basis it uses; the operator would answer with a number it already prints. The seventeen documents read on 24 and 25 November 2026 contain no measurement point for the 6.4 MW, no conversion of it into a billed demand, and no public Kenyan count of data-centre load at all. That is a count over a named set, not a verdict on the world.
It is enough to establish who owns the definition today, and it is not the state.
Member Briefing
Read the full trend briefing
Members read the full briefing with the source notes behind every finding.
Strategic Circle
A daily briefing in your language, built from changes we have verified.
Join for USD 20/monthCancel anytime.
Members also get the full research library, a daily briefing on the networks they follow and the private forum.