Summary
- Digital Realty prints a 2025 portfolio PUE of 1.38 to two decimals with a population footnote, and prints neither the total-facility energy nor the IT-equipment energy that the ratio divides.
- The standard that defines PUE fixes three measurement categories by where IT energy is taken, and states that the calculated figure should not be used to compare data centres; the disclosure names no edition and no category.
- Europe takes both operands privately and publishes only a weighted average, which is how a continental PUE of 1.36 with a letter-grade ladder exists while no building behind it does.
Start on the page most readers will see. Digital Realty's sustainability page states the entire claim in a headline and a decimal point: "1.38 Our portfolio Power Usage Effectiveness (PUE)" (sustainability page). No period. No count of buildings. No kilowatt-hour. No standard. The page does say the company tracks energy and water monthly and sets site-specific PUE and WUE targets, which sounds like a method until you go looking for the arithmetic underneath it.
The report says a little more, and not much more. The 2025 Impact Report prints "2025 Average annual PUE 1.38" with a footnote that is the most informative sentence in the whole disclosure: "Weighted average for data centers operational for ≥12 months and with utilization ≥20%" (2025 Impact Report). That sentence describes who is inside the average. It says nothing about what was measured. Beside it sit three regional figures — APAC 1.38, EMEA 1.31, North America 1.41 — and, separately, an average design PUE of 1.20 for the 196 MW of IT capacity delivered in 2025: a promise about buildings entering service, not a report on buildings that ran. The report landing page and the 27 May 2026 release repeat the same pair (landing page, release).
The same breath carries 0.59 portfolio WUE and 93 per cent global renewable electricity coverage. Water use and renewable share are different quantities from efficiency, but they are printed together, and the boundary that would make them comparable — which facilities, which months, which energy sources counted — is named for none of them.
PUE does have a definition, and the definition is a division. ISO/IEC 30134-2 calls it the "ratio of the data centre total energy consumption to information technology equipment energy consumption, calculated, measured or assessed across the same period" (ISO/IEC 30134-2:2016). The same standard writes both terms as annual kilowatt-hours, notes that where the only energy source is the utility the total is "determined by the location of the utility meter", and adds two sentences the industry quotes less often: by definition the calculated PUE is always greater than 1, and "PUE should not be used to compare different data centres".
Then come the categories. The January 2026 second edition keeps three of them in clause 6.2 — Category 1 basic resolution, Category 2 intermediate resolution, Category 3 advanced resolution (second-edition preview) — and the working distinction between them is where the IT energy is taken: at the uninterruptible power supply output, at the power distribution unit output, or at the equipment input (Open Compute Project). The top of the fraction barely moves. The bottom of it moves by design. One building, three honest readings, three different numbers, and the standard's own architecture is the reason.
Digital Realty's disclosure names none of the three. It says PUE measurement has been "standardized ... in alignment with ISO international standards", which is a gesture rather than a citation. A standard has an edition and a category label; neither is printed beside the figure.
What the printed numbers imply is easy to state and impossible to check. On 10 MW of IT load, the design figure of 1.20 carries 12 MW of total energy and 2 MW of overhead; the portfolio figure of 1.38 carries 13.8 MW and 3.8 MW; the North American figure of 1.41 carries 14.1 MW and 4.1 MW (mine). The gap between the design promise and the operating portfolio is 1.8 MW on 10 MW of load. The printed regional spread between North America and EMEA is a full megawatt on the same 10 MW.
None of those pairs shares a population: 1.20 covers capacity delivered in 2025, 1.38 covers sites at least a year old and at least 20 per cent utilised, and the regions are subsets of that second group.
The numerator exists somewhere. Two third-party tables transcribe 12,805,833 MWh of total energy consumption for 2025 from PDF page 96 of the same report (one transcription) and then disagree about the row beneath it, which one calls total renewable energy consumption and the other electricity consumed (another). If the first row were the total-energy term behind 1.38, the IT-energy term would be 9,279,589 MWh and the overhead 3,526,244 MWh — mine, and conditional on a perimeter that no page read for this piece states. The report's own contents page puts environmental data at printed pages 91 and 92, with the assurance statement at 93 (report); a report index records 97 pages, a 1 January to 31 December 2025 period, and a Cventure limited assurance over the appendix (index entry). The appendix rows themselves did not come back in this reading. That is a limit of the reading, not proof that a row is absent from the report.
The European regime does the opposite of the company, then halves it. Delegated Regulation (EU) 2024/1364 applies to data centres with an installed IT power demand of at least 500 kW. Its Annex II measures total energy at the input of the data centre system, before the supply transfer switchgear, counting electricity, fuels and other sources; it measures IT energy by the category 1 methodology of EN 50600-4-2 at every uninterruptible power supply. Annex III sets the formula. Annex IV publishes aggregates at Member State and Union level, weighted by total energy consumption, with a three-data-centre minimum for any breakdown, and Article 5(5) keeps the facility rows confidential (Delegated Regulation (EU) 2024/1364). The regulator holds both operands and prints the average.
Which is why the Commission can publish an average reported PUE of 1.36 for 2024 across 770 reporting data centres — roughly 36 per cent of the estimated in-scope population — with 681 returns it deems reliable, national averages from 1.15 to 1.66, and a grading ladder that calls anything below 1.2 excellent, 1.2 to 1.5 good and above 1.5 a candidate for improvement (Commission report). The dashboard behind it refreshes monthly with the aggregates and nothing finer (DG ENER). Every step in that chain is lawful. The sum is a public that cannot recompute any of it.
Two documents in this file cannot both be right about comparison. The standard that defines the metric says PUE should not be used to compare different data centres. The company prints a regional comparison, and the Commission prints a continental ladder with grades attached. Neither page supplies the operands that would let a reader test the comparison; the ladder grades a number whose two halves are filed privately and printed nowhere.
For a colocation customer the omission is not academic. PUE's denominator is the customer's own draw and its numerator is the operator's overhead: the buyer pays for the first and is asked to accept the second on trust. A tenant whose lease references an efficiency figure should ask for three things this disclosure does not print — the total-energy and IT-energy rows in megawatt-hours, the measurement category, and whether the number describes the building, the campus or the portfolio. A buyer who gets the two rows holds a number anyone can divide. A buyer who accepts 1.38 holds a decimal point. Digital Realty's record in our directory is here.
None of this makes the metric a fraud, and none of it needs a villain. It makes the printed figure a presentation: two decimal places of precision resting on a division whose halves are held by the party being measured and, in Europe, by a regulator that keeps them confidential. The standard itself warns against the comparison the market performs anyway. Print the megawatt-hours and the boundary, and 1.38 becomes checkable by anyone with a calculator. Until then it is a number the operator can print and no reader can rebuild — which is precisely the difference between a measurement and a claim.
Member Briefing
Read the full trend briefing
Members read the full briefing with the source notes behind every finding.
Strategic Circle
A daily briefing in your language, built from changes we have verified.
Join for USD 20/monthCancel anytime.
Members also get the full research library, a daily briefing on the networks they follow and the private forum.