Summary
- Prysmian's data sheet prints 547 amperes direct in ground at 300 square millimetres and states no soil thermal resistivity, no ground temperature and no depth. The missing values sit in AS/NZS 3008.1.1, at 1.2 °C·m/W, 25 °C and 0.5 m.
- IEC 60287-1-1 writes the rating as a heat equation, then says the dry-out resistivity and critical soil temperature "must be determined from knowledge of the soil conditions" and "may be agreed between manufacturer and purchaser".
- Of the five condition blocks read, three name 20 °C as the reference ground temperature, one 15 °C and one 25 °C; four print a soil thermal resistivity — 2.5, 1.5, 1.2 and 1.2 K·m/W — and the fifth prints none in the passage read.
- The Australian catalogue prints capacitance and charging current per kilometre beside every rating row, so the route-length limit is computable from its own cells: 547 amperes divided by 1.52 amperes per kilometre gives 359.9 kilometres.
The number on the page and the three conditions that are not
The data sheet is one page of electrical characteristics for a copper 19/33 kV three-core heavy-duty screened unarmoured cable. One row gives amperes per conductor size: 195 at 50 square millimetres, 240 at 70, 285 at 95, 330, 370, 410, 486, and 547 at 300. In singleway ducts the same 300 square millimetres carries 452. Four installation descriptions follow — in free air, in duct, in trench, in ground with protection — and then the page stops.
No soil thermal resistivity. No ground temperature. No depth. This is not an omission peculiar to one product page; it is the design of a catalogue. The medium voltage catalogue says where the numbers come from: they follow AS/NZS 3008.1.1. Read that standard and the three missing values arrive at once — 25 °C ambient soil, 0.5 m depth measured to the centre of the cable or of the trefoil group, and 1.2 °C·m/W soil thermal resistivity, with single-core cables touching in trefoil or touching in flat formation and multicore cables laid singly.
So 547 amperes is a rating for a trench that is twenty-five degrees warm, half a metre deep, filled with soil of 1.2 and holding one multicore cable. Change any one of those and the number moves. The standard says so itself in the same breath: it calls 1.2 an average across soil types, assumed to reach its maximum at the time of maximum load, notes that clay and peat may be as low as 0.8 and well-drained sand as high as 2.5, warns that its depth factors assume a constant effective resistivity between half a metre and three, and recommends at least 200 mm of selected or stabilised backfill where the soil exceeds 1.2.
That last sentence is the whole story in miniature. The remedy for a bad soil is not a bigger conductor. It is imported sand, chosen and compacted.
The standard writes the rating as a temperature
IEC 60287-1-1 does not define a current for a conductor. It solves a thermal circuit and reads the current off it: the temperature rise above ambient equals the sum of the losses, each multiplied by the thermal resistance between it and the next colder thing, ending with T4, the thermal resistance per unit length from the cable surface to the surrounding medium, taken from a different part of the standard entirely.
The ambient in that equation is likewise not a property of the cable. The same part defines it as the temperature of the surrounding medium under normal conditions at the point of installation, including the effect of local heat sources but excluding the cable's own heating.
Then comes the sentence that makes this an article. Where the soil dries out partially, the standard uses a two-zone model with a ratio between dry and moist resistivity, a critical soil temperature and a critical temperature rise, and rules that the lower of the two ratings governs. It then says of the critical temperature and the dry-out resistivity that they "must be determined from knowledge of the soil conditions", and that suitable soil parameter values "may be agreed between manufacturer and purchaser".
The instrument that defines the rating explicitly declines to fix the term the rating most depends on. It gives that term to the ground, and then to a conversation.
A standard that recommends, a country that decides
What fills the gap is a hierarchy, and IEC 60287-3-1:2017 sets it out plainly: its general values are superseded by specific national requirements. The same part explains why the soil value cannot simply be declared — thermal resistivity is highly moisture-dependent and varies with soil type, topography, meteorology and cable loading, so measured values are recommended. It supplies classes to think with: 0.7 K·m/W for very moist, continuously moist ground, 1.0 for regular rainfall, 2.0 for ground where it seldom rains, 3.0 for very dry ground with little or no rain.
It also supplies a default depth where none is given — one metre — and default ground temperatures at that depth, 10 to 20 °C in temperate climates, 15 to 30 subtropical, 25 to 40 tropical. And its annex prints what countries actually do: Germany at 1.0 K·m/W average with 2.5 in the dry zone, 20 °C maximum, 0.7 m below 60 kV and 1.2 m at and above it; Austria at 1.0 and 2.5, 20 °C, and 0.7, 0.8 or 1.2 m by voltage class; France at 1.20 nominal in summer with 2.5 in the dry zone, and 20 °C at 20 kV.
The United Kingdom row of that annex did not render in the preview read here, so the British value enters below second-hand, through the institution that publishes the wiring regulation.
One further fact from that annex deserves a sentence of its own: the standard's own default depth of one metre appears in none of the five manufacturer condition sets read.
Five routes for one copper
Set the documents side by side and the same manufacturer answers the open question five ways, because five national practices answer it first.
- ASEAN, low voltage (Electrical Information for Low Voltage Cables): method D1 is a cable drawn into a 100 mm plastic, earthenware or metallic duct laid in soil of 2.5 K·m/W at 0.8 m; method D2 is the cable in direct contact with the same soil at the same depth, and the D2 tables are headed 20 °C in ground.
- ASEAN, medium voltage (Rating Factors for XLPE/EPR Insulated MV Cables): 90 °C conductor, 30 °C in air, 20 °C in ground, 1.5 K·m/W soil, 0.8 m depth, with layouts for one multicore cable, three single-core cables flat and three in trefoil.
- United Kingdom (a distribution-cable data sheet): air 25 °C, ground 15 °C, 500 mm to the centre of the cable group, soil 1.2 °C·m/W, and three columns — in air, direct in ground, drawn in duct. A three-core 185 square millimetre aluminium cable reads 385, 355 and 300 amperes in those three columns.
- Australia: 25 °C soil, 0.5 m, 1.2 °C·m/W, through AS/NZS 3008.1.1.
- Italy (Dati tecnici media tensione): 20 °C buried, 30 °C in air, depths of 0.8 m for 3–10 kV, 1.0 m for 15–30 kV and 1.2 m for 45 kV, metallic screens interconnected and grounded — and no soil thermal resistivity in the passage read, which is a limit of the reading rather than a finding that the document prints none anywhere.
Four soils: 2.5, 1.5, 1.2 and 1.2 K·m/W. Three ground temperatures: 20, 15 and 25 °C, with the Italian block naming 20. Two depths plus a third document that varies depth by voltage class. One page prints a distinct column for a cable drawn into a duct; another collapses direct burial and duct into a single reference method. Every one of those tables is a correct calculation of a route.
The UK comparison page is the manufacturer explaining the disagreement in its own words:
In both instances, the ratings are derived from calculation methods outlined in IEC60287. BS7671 publishes ratings taken from the harmonised document, HD 60364-5-52. Prysmian publishes ratings from the ERA 69-30 series of publications.
It then sets the two bases beside each other: the harmonised document at 20 °C soil, 2.5 K·m/W and 700 mm with no distinction between ducted and direct-buried; its own at 15 °C, 1.2 K·m/W and 500 mm with the two cases calculated separately and ducts rated lower. It advises that its own figures are usable at 500 mm with suitably compacted backfill, and recommends third-party soil analysis where conditions are unknown. The page carries no date, so the two bases are attributed to it as read, not to a numbered edition of either document.
One country's quarrel, in three factors
The reconciliation of that quarrel is published by the Institution of Engineering and Technology, and it is worth reading slowly because it converts the whole argument into arithmetic. The harmonised document uses 2.5 K·m/W as a precautionary worldwide value where soil type and location are unspecified. The supply industry's ERA 69-30 assumes 1.2, matching the UK value in the standard's own national annex. The differences land in three places, and the IET prints a factor for each: 20 against 15 °C ground, factor 1.05; 2.5 against 1.2 K·m/W soil, factor 1.40; 0.7 against 0.5 m depth, factor 1.03.
Multiply the three and you get 1.514. The regulation's rating for a cable therefore stands about 51 per cent above the manufacturer's for the same cable, and the manufacturer's is about two-thirds of the regulation's. The three factors are the IET's; the product and the two readings of it are mine.
The same article supplies two details that stop the argument from being abstract. 120 thermal ohm-centimetres equals 1.2 K·m/W — the unit the older literature quotes and the unit the modern one assumes, exchanging at a factor of 100 — and continuous heavy load can dry the soil and raise its resistivity, which is why a cement-bound sand backfill fixes conductivity but is rarely cost-effective at small conductor sizes.
The ladder, climbed
The correction tables are the part of this story the seller gets most right, and their internal arithmetic is the part that should worry a buyer most.
Start with the harmonised table for soil resistivity, Table B.52.16, which applies to reference method D and, in that table, does not distinguish a buried cable from a ducted one: 1.28 at 0.5 K·m/W, 1.20 at 0.7, 1.18 at 1.0, 1.10 at 1.5, 1.05 at 2.0, 1.00 at 2.5 and 0.96 at 3.0. The manufacturer's low-voltage sheet reproduces the same table but splits it by method, and its direct-buried column is far steeper: 1.88, 1.62, 1.50, 1.28, 1.12, 1.00, 0.90.
Divide the ends of that column and one conductor carries 2.09 times as much in continuously moist ground as in ground where it seldom rains — both cells from one table in one document, the division mine. Applied to a printed 100 amperes, that is 188 amperes against 90, a 98-ampere difference on the same drum label.
The medium-voltage sheet behaves the same way with different numbers. Its soil ladder runs from about 1.34 at 0.7 K·m/W to 0.74 at 3.0, a ratio of 1.81; its ground-temperature ladder runs from 1.07 at 10 °C to 0.76 at 50, a ratio of 1.408; its depth ladder runs from about 1.04 at half a metre to 0.90 at three. Those three ratios are mine, taken from cells in one table each. Before grouping has been counted at all, the soil alone moves a medium-voltage rating by 81 per cent and the ground temperature by 41 per cent.
Two cautions belong beside those cells. The depth ladder is not monotonic in the direction intuition suggests — 0.90 at three metres against 1.04 at half a metre is 0.865, so deepening a trench from half a metre to three leaves 86.5 per cent of the rating, and the last stretch of depth costs current rather than buying it. And one column of the extracted medium-voltage soil table is internally inconsistent, showing 1.14 and then 1.15 for adjacent rows at 0.9 K·m/W, which is why the ratios above are built from the 0.7 and 3.0 columns instead.
Grouping is the term that falls out of these excerpts rather than into them. The medium-voltage sheet's grouping and spacing factors were not visible in the passage read. The UK data sheet states the depth to the centre of the cable group and nothing further about how many cables the group holds. AS/NZS states its base arrangement precisely, and a cable buyer who does not know his own arrangement has no way to use it.
The other thing the sheet cannot print
Every term in the rating equation except one is a decision taken upstream of the site: conductor resistance, insulation thickness, the thermal resistances inside the cable, the standard's structure, the national code's reference depth, the manufacturer's choice of what to tabulate. The soil is not. It is a property of a particular trench, at a particular moisture content, in a particular season, and it belongs to the party who dug it.
IEC 60502-2:2005, the medium-voltage cable standard, states that consequence without softening it: under continuous full load the soil's thermal resistivity may rise through drying out, so the conductor may exceed its maximum temperature unless provision is made. Its annex supplies the correction tables for ground temperature, for depth of laying of direct-buried cables, and for soil resistivities of direct-buried single-core cables, split by installation and by cable type. The numeric factors in the copy read here were not extracted, which is a limit of this reading and not a claim about the document.
A circuit that runs near its rating therefore heats the material that sets its rating. The ladders treat the soil as a constant and the standards say it is a variable that gets worse under load. That is the whole mechanical argument, and neither the data sheet nor the brochure has a column for it.
A length limit disguised as a current
The second printed quantity in this catalogue is the one that does the multiplication the ampere column refuses.
Beside every rating row, the Australian pages carry capacitance phase-to-earth in microfarads per kilometre and charging current at rated voltage and 50 Hz in amperes per phase per kilometre. For the 19/33 kV three-core cable the range is 0.834 amperes per kilometre at 50 square millimetres to 1.52 at 300, with capacitance of 0.140 to 0.255 microfarads. For the 6.35/11 kV three-core it runs 0.422 to 1.03.
Those figures recompute. Charging current is the cable's own capacitance working on its own rated voltage: two pi times frequency times capacitance times phase voltage, times length. At 300 square millimetres, 33 kV divided by the square root of three is 19.053 kV, and two pi times 50 times 0.255 microfarads times 19.053 kV is 1.526 amperes per kilometre against a printed 1.52. At 25 square millimetres on the 11 kV cable the same arithmetic returns 0.423 against a printed 0.422. Both close inside half a per cent on operands printed on the same pages; the recomputation is mine.
The catalogue performs, in the capacitance column, exactly the multiplication the ampere column leaves to the reader.
Now the limit. Divide the rating by the per-kilometre charging current and you have the length at which the circuit's own capacitance consumes the current the factory sold: 547 divided by 1.52 is 359.9 kilometres. Both operands come from the one data sheet; the quotient is mine. That is why the constraint has never troubled a distribution network, and why it governs a transmission route.
The shape of the limit is described elsewhere by ELEK Software: a critical length where charging current equals the source's rated current, cable shunt capacitance 10 to 20 times that of an overhead line, alternating-current routes typically limited beyond about 40 km below 220 kV and about 20 km at and above it, and shunt reactors used on long runs.
And the constants behind the capacitance are printed by the manufacturer in an older calculation excerpt, revision 4 dated 21 June 2006, hosted third-party and OCR-garbled: charging current as two pi f C E, capacitance from 7.354 times the specific inductive capacity over the logarithm of the diameter ratio, and typical dielectric constants of 3.5 to 8.0 for PVC, 2.5 to 4.0 for EPR, 3.0 to 6.0 for polyethylene, 2.1 to 2.3 for XLPE and 3.3 to 3.7 for impregnated paper. Only the constants and the shape of the relations are taken from it here.
The eight things a reader would need
Set the whole exercise as a checklist and the finding becomes a count. To reproduce a printed rating at a real site a reader needs eight things.
The base current: printed, on every row. The derating tables: printed, and generously, in three different documents. The charging current or route-length term: printed per kilometre, never as a limit, and computable from its own cells. The soil thermal resistivity: printed four different ways by the same seller and in a fifth document not at all. The ground temperature: 20 °C, 15 °C, 25 °C, 20 °C, 20 °C. The depth: 0.8 m, 0.8 m, 500 mm, 0.5 m, and three values by voltage class. The grouping: stated exactly by the Australian standard, stated as far as the centre of the group by the UK data sheet, and not visible in the medium-voltage excerpt.
And lastly the worked example — one page anywhere that takes a trench, reads off its soil, its depth, its grouping and its ambient, and performs the multiplication once in public. In the sixteen documents read for this article, that page does not exist.
The high-voltage catalogue makes the point by omission. Its columns read Current Rating in air at 30 °C and Current Rating in Ground at 20 °C, with 517 amperes in ground and 699 in air for a 36/66 kV single-core 240 square millimetre cable, rising to 991 and 1580 at 1200 square millimetres; and 505 amperes in ground at 240 for the 87/150 kV construction, up to 1015. The soil, the depth, the formation and the screen bonding behind those ground ratings were not in the excerpts read, so those numbers sit in this article quoted and uncompared. They are the cleanest illustration available of what a bare ampere column is: a true number whose conditions are somewhere else.
What to write into a specification
None of this makes the tables dishonest. Each is a correct calculation of a stated route, and a buyer who knows his route can use them. The practical consequence is a short list of sentences that belong in the specification rather than in the brochure.
The soil thermal resistivity the rating assumes, and the survey that establishes the site's. The ground temperature at the depth of laying, not the air temperature. The depth to the centre of the group, and whether the cable is buried direct or drawn into a duct. The number and spacing of loaded circuits in the same trench. The backfill material and its compaction. And, on long routes, the capacitance per kilometre and the length at which charging current has to be dealt with.
Those sentences cost a soil survey and a line in a tender. The alternative costs a feeder that reaches its nameplate only in a wet spring.
Prysmian S.p.A. is tracked in the BTW directory as prysmian-s-p-a-it.
Member Briefing
Read the full trend briefing
Members read the full briefing with the source notes behind every finding.
Strategic Circle
A daily briefing in your language, built from changes we have verified.
Join for USD 20/monthCancel anytime.
Members also get the full research library, a daily briefing on the networks they follow and the private forum.