Summary
- One Data Center America prints four availability figures on four of its own pages: 100 per cent as a stated priority on the homepage, 99.99 per cent on the rack colocation listings, 99.9 per cent on the dedicated servers page, and 99.9 per cent as a goal in the service level agreement. Only the agreement page defines how any figure is measured.
- That definition counts a monthly percentage of network connectivity, pays credits in three bands with two unprinted gaps between them, excludes Scheduled Maintenance by name without a notice period, and asks for a claim within five working days of an outage that belongs to a month which has not yet closed.
Four pages, three values. The rack colocation listings offer a "99.99% Uptime Guarantee" on the quarter, half and full racks, and the 10U listing reads "10U Rack Space 10MB Bandwidth Unlimited Traffic 99.99% Uptime Guarantee" (rack colocation). The dedicated servers page advertises a "Fast, Multi-homed, Redundant Network with network up-time SLA of 99.9%" (dedicated servers). The homepage sets the ambition higher: "To offer 100% Up-time is our #1 priority" (homepage). The service level agreement calls 99.9 per cent a goal (service level agreement). None of the four pages cross-references another, and none of them says which figure binds the rack customer who paid for a rack.
The brand is One Data Center America, and the address in the directories is 350 S. Milliken Ave in Ontario, California: Baxtel prints it for the facility it designates ODCA ONT-1 (Baxtel), DataCenterMap prints it with Suite E and the postal code (DataCenterMap), and the operator's own pages print no street address at all. The homepage announces a second Ontario site, ONT-2, without one either. The directory record this coverage attaches to is Ontario Datacenter LLC, and an earlier btw.media briefing of 29 September 2026 traced how the name and the network came apart there (prior briefing): California LLC file 201132110226, FCC Form 499 filer 831725 reading "No Longer Active as of 10/1/2016", ARIN handle ODL-10 and ASN 19598 announcing no routes, and successor One Internet America, LLC (AS54623) holding the same street address under the same chief executive. That briefing is about identity and routing. It prints no availability figure, no credit schedule, no measurement period and no claim clock. This article asks what the operator promises and whether a stranger can check the promise, and the answer starts with a single sentence.
"SLA is based on the percentage of a particular month (based on 24-hour days for the number of days in the month) that the customer's services have network connectivity." That sentence, on the agreement page, is the entire measurement design (service level agreement). It carries a unit (a percentage), a period (a calendar month), a weighting rule (every day counts as twenty-four hours, whatever the month's length) and a subject (the customer's services having network connectivity). It carries no accuracy target, no sampling rule, no named monitor, no reporting obligation on the operator and no published output. The page also states the level as an intention rather than a commitment: "One Data Center America goal is to ensure 99.9% of services available for all of our customers."
Read what the subject leaves out. The measured thing is network connectivity. Power, cooling, humidity, fire suppression, physical access, cross-connect delivery and the rack itself appear nowhere in the measurement. That is not a quibble about words. A colocation customer buys a rack, a power feed and a port, and the only availability definition the operator publishes covers the port. The rack page's 99.99 per cent carries no definition of its own, so either it inherits the network-connectivity definition or it has none at all, and the reviewed pages never say which.
The credits are printed as a schedule and read like one until the boundaries are checked: "Service Credits \u2013 Service Uptime 95% \u2013 99.9% \u2013 10% Credit 90% \u2013 94.9% \u2013 15% Credit 89.9% or below \u2013 100% Credit" (service level agreement). In numbers: 95 to 99.9 per cent earns a tenth of the month's charge, 90 to 94.9 earns fifteen per cent, and 89.9 or below earns the month back. Two readings of that schedule are mine, and both are checkable against the page. First, a customer scoring 94.95 per cent, or 89.95, falls between printed bands, and the page says nothing about the case; the gaps are one tenth of a point wide and a customer can land in one. Second, the top band stops at exactly the number the same page calls its goal, so 99.9 per cent is simultaneously the target, the lower edge of the 10 per cent credit band and the figure the dedicated servers page sells as a service level. A customer scoring exactly 99.9 has met the goal and, on a literal reading of the schedule, qualified for a credit.
Put the schedule on a calendar and it changes character. In a thirty-day month of 720 hours, the 99.9 per cent goal permits 43 minutes without connectivity. An outage of one hour takes the month to 99.86 per cent, inside the top band, and earns a tenth of that month's charge. Reaching the 15 per cent band needs the month to fall to 94.9 per cent, which is 36.7 hours offline. Reaching the 100 per cent band needs 89.9 per cent, which is 72.7 hours: three days without connectivity in a thirty-day month. All three conversions are mine, and the page prints no such table. That is what makes them worth setting down.
A customer reads "100% Credit" on the page and reasonably imagines it is the reward for a bad afternoon. It is the reward for a bad fortnight.
A credit is also not a repair. A customer who collects the whole month back has still lost the month, and the schedule promises no restoration, no engineering response, no root cause and no report. It prices the outage at, at most, the invoice for the month in which it happened. Everything the customer actually buys when buying redundancy is outside this instrument, and the operator never represents otherwise.
Then the clock, which is where the schedule stops being a comfort. "You must claim your credit within 5 working days from when the outage occurred", filed through "our ticket support system inside your account" (service level agreement). The measurement window is a month. Five working days is at least five calendar days, and more whenever a weekend or a public holiday falls inside it. So an outage in the first twenty days of a thirty-day month puts the claim deadline before the close of the very month the percentage is computed from. The customer must assert a number before the operator has one. The customer must describe an outage whose weight in the month's percentage is still being determined, and must do it on the operator's ticket system, in the operator's format, with the customer's own monitoring as the evidence. The arithmetic is mine; the ordering is the page's.
The second half of the clock is longer. "your credit will be applied within 30 to 60 days from when the ticket is submitted." Chain the intervals and an outage on the first of a month can be claimed by about the tenth and paid somewhere between five and ten weeks after the event. Nothing on the page obliges the operator to acknowledge the claim, dispute it or explain a refusal. The schedule prints a payment window and no decision window, so a customer who hears nothing for two months cannot tell whether the claim was accepted.
The exclusions do the quiet work. "The customer shall not receive any credits" governs a list that names Scheduled Maintenance beside circumstances beyond the operator's control, DDoS and DOS attacks, viruses or hackers, interruption or unavailability of telecommunications or third-party services, third-party software failure, external DNS issues and DNS propagation, and "Failure to access One Data Center America Networks, unless the failure is caused into our Datacenter" (service level agreement). Two features matter more than the length of that list. Scheduled Maintenance is excluded by name, and the page prints no notice period, no notice channel and no list of past or planned maintenance windows; without a notice obligation the exclusion has no perimeter a customer can test. And the clause excluding a failure to reach the network unless the failure was "caused into our Datacenter" states the perimeter of the entire promise in one sentence: the operator's own building is inside it, the path to the building is outside, and the sentence separating them was not drafted with a diagram in mind.
Consider what an unbounded maintenance exclusion can absorb. Twelve hours of maintenance in a thirty-day month is 1.7 percentage points. A month that a customer experienced as 98.3 per cent connectivity is, on the page's arithmetic, a whole month, because the maintenance never entered the count. Since the 10 per cent band only starts at 36.7 hours, the exclusion can swallow three maintenance windows of that size and the schedule still owes nothing. The customer who disputes it is told the time was scheduled. The page that would have shown when cannot be produced, because no version is kept.
Two further clauses give the operator the last word. It "reserves the right to amend the above at any time", with no notice period, no version number and no archive, so a customer cannot establish what the schedule said when the outage happened (service level agreement). And it "will void SLA credit when third party monitoring scripts can easily be manipulated to give false results or are highly inaccurate." The customer supplies the evidence and the operator grades it. The page defines neither "easily manipulated" nor "highly inaccurate", describes no appeal, and offers no alternative to the customer's monitoring, such as a shared measurement or a published monthly figure. Neither clause is unusual in this market. Together they mean the schedule is a floor that can move and a claim that can be refused on the strength of a judgement the page never explains.
What the reviewed set does not contain matters as much as what it does. Baxtel prints ODCA ONT-1 as "Operational" and "Fully operational facility", with no timestamp, no methodology and no incident log (Baxtel). DataCenterMap prints the address and nothing about availability (DataCenterMap). Across the nine documents reviewed for this article, four operator pages and five third-party or prior editorial pages, no page outside the operator's own site records an outage, a downtime event or a maintenance notice at 350 S. Milliken Ave. Baxtel's field is current-state only, so it can neither corroborate nor refute a past event, and the silence is a fact about those nine documents rather than a finding about the building.
The directories fill the gap with numbers the operator does not publish, and the numbers do not agree. ColocationM carries a "Live Facility Status" badge reading "Operational 99.99% Current Uptime" and asserts "Tier III Certified" beside a "99.99% Uptime SLA" (ColocationM). None of that matches the operator's own 99.9 per cent goal or its 95, 90 and 89.9 bands; the badge names no monitor and no measuring period, and the certification claim appears nowhere on the operator's own pages. Godatacenters prints 10.3 MW and 36 kW per rack for the same street address while flagging the record "Availability to confirm" and its power figure as imported and unverified (Godatacenters). The operator publishes no capacity figure at all, so a reader comparing sites is comparing directory guesses. A live status badge is not an incident record. It is a picture of a green light with no bulb behind it.
I came to this operator looking for a different instrument, and the correction belongs in the record. The expectation was a reliability ranking that excluded the worst days by a threshold the operator sets: so many days above a declared severity, removed from the denominator, with the removed days still visible somewhere. The reviewed pages contain no such rule. There is no per-day count, no severity grade and no annual ranking. The only measurement is a monthly percentage, and the only thresholds printed beside it are the credit bands. That correction is worth publishing for its own reason.
A monthly percentage cannot be reconstructed after the fact from anything else on the site, because the operator publishes no daily or monthly series; the schedule is therefore the only thing that turns a number into money, and the schedule carries that weight alone.
So the test a stranger can actually run is narrow, and worth stating plainly. The site prints 100, 99.99 and 99.9. One page defines the measurement. That definition counts the network and not the building. The credits begin at a boundary the stated goal sits on. The claim falls due within days of an event whose month has not closed. The maintenance exclusion has no notice perimeter. The schedule can be amended without a version. What is missing is the smallest possible addition: a dated version of the page, a monthly figure for each month, a list of the days removed from the count, and a count of claims filed, granted and refused.
Four lines would turn a promise into a record. Until they appear, this is a good promise to publish and a hard one to check, and the distance between those two things is the whole distance between a service level agreement and an assurance.
Member Briefing
Read the full trend briefing
Members read the full briefing with the source notes behind every finding.
Strategic Circle
A daily briefing in your language, built from changes we have verified.
Join for USD 20/monthCancel anytime.
Members also get the full research library, a daily briefing on the networks they follow and the private forum.