Summary
- A Saft Sunica.plus cell is sold twice on one printed row: 1,830 ampere-hours at the 120-hour rate and 1,700 ampere-hours at the five-hour rate, figures 7.1 per cent apart that permit currents 22.3 times apart.
- The rate conversion is not a coefficient in any of the ten documents read on 26 November 2026; it is a second table column, and the ageing divisor of 0.7 is a calendar with the number of years removed.
A Saft Sunica.plus cell type called SUN+ 1830 is sold as 1,830 ampere-hours. On the same printed row of the same 2023 datasheet, the same cell is sold as 1,700 ampere-hours. The two figures sit 7.1 per cent apart, since 1 − (1,700 ÷ 1,830) = 0.0709, and the gap is not a revision or a tolerance. It is the hour rate. The 1,830 figure is what the cell delivers over a 120-hour discharge; the 1,700 figure is what it delivers over a five-hour discharge; both run down to 1.0 volt per cell (Sunica.plus datasheet, February 2023).
Turn those two capacities into the currents they permit and the row stops looking like a rounding. 1,830 ampere-hours over 120 hours is 15.25 amperes. 1,700 ampere-hours over five hours is 340 amperes. The capacities differ by 7.1 per cent. The currents differ by 22.3 times. Both divisions are mine; both operands are printed on that row.
That single row is this article in miniature. A stationary battery is not sold as a quantity of electricity. It is sold as a quantity of electricity at a named rate, and the rate is where the story lives — because the rate is the one condition of the four that changes what the buyer can actually run.
The sentence that states five conditions
Saft's solar manual devotes a numbered clause to the definition, and the clause is unusually honest:
The Sunica.plus battery capacity is rated in ampere hours (Ah) at the C120 discharge rate. It is the quantity of electricity supplied for a 120 hour discharge period to a cut-off voltage of 1.0 volt per cell after being fully charged. (Sunica.plus technical manual, June 2012)
Five conditions are named in two sentences: the chemistry, the 120-hour rate, the 1.0 volt per cell cut-off, the fully charged starting state, and — two sections later — the temperature at which the figure holds, printed as a range: "Cell capacity ratings are defined at +20°C to +25°C (+68°F to +77°F)."
The company's other stationary family states the same five conditions with different numbers. This is the 2012 edition with a December 2018 cover, hosted by a distributor:
Its rated Ah is the quantity of electricity at + 20°C (+ 68°F) which it can supply for a 5 hours runtime to 1.0 V/cell after being fully charged. This is in accordance with both IEC 62259 and IEC 60623 standard. (Uptimax technical manual)
And the same sentence five years earlier, from a June 2010 edition, citing one standard rather than two:
The Uptimax battery capacity is rated in ampere-hours (Ah) and is the quantity of electricity at +20°C (+68°F) which it can supply for a 5 hour discharge to 1.0 V/cell after being fully charged. This figure is in agreement with the IEC 62259 standard. (Uptimax technical manual, June 2010)
So the two families are not rated at the same rate, and they are not rated at the same temperature either. One is a 120-hour cell at +20 to +25 °C. The other is a five-hour cell at +20 °C, with its published amperes valid over a ten-degree band of ±5 °C (Uptimax datasheet, January 2023).
I went into this expecting a house convention. A maker rates capacity at five hours or at ten, at 25 °C, to a fixed end voltage, and the interest lies in how far a data hall's duty sits from those numbers. That premise was wrong twice over, and the corrections are worth printing because they are the article.
Two families, twenty-four hours apart
The hour rate is a product decision, not a company habit. Uptimax is rated at C5; Sunica.plus is rated at C120. The two rates sit a factor of 24 apart, which is 120 ÷ 5 and nothing more. One family is characterised down to a 30-minute rate in its M range and a one-hour rate in its L range; the other is characterised for a 120-hour discharge and priced in 120-hour ampere-hours.
The 2007 edition of the solar manual even gives the reason for the choice, in the sentence after the definition: the 120-hour figure "was chosen as being the most useful for sizing photovoltaic applications" (Sunica.plus technical manual, May 2007). The 2012 edition drops the reason and keeps the number, adding only the letters that name it: C120.
That is a defensible engineering decision. A solar array with an eight-day autonomy requirement draws its battery over days, so a 120-hour rating describes the duty. A substation switchgear duty draws the same chemistry over seconds and minutes, so a five-hour rating is already generous and a 30-minute characterisation is what the load wants. Two products, two rates, one chemistry.
What the decision produces, however, is a catalogue in which the same adjective does two jobs. In the technical manual's own cell table the five-hour column is headed "Rated capacity 5 h - 1.00 V C5 Ah" and the 120-hour column is headed "Nominal capacity 120 h - 1.00 V C120 Ah". The word rated belongs to the five-hour column in the table and to the 120-hour rate in the sentence above it. The word nominal belongs to the 120-hour column. A reader skimming for a rating has two places to find one, and the manual's own two usages point in opposite directions.
The conversion is a column, not a coefficient
I expected a coefficient table — the kind of rate factor a buyer multiplies a rated capacity by to obtain a capacity at his own discharge time. There is no such table in the ten documents read on 26 November 2026. The conversion is a second column beside the first, printed in the technical manual, printed again in the installation and operating instructions, and printed again in the datasheet.
The installation sheet puts it most plainly, with the two ratings adjacent, a charging current defined off the five-hour column, and a water top-up quantity in the same row (Sunica.plus installation and operating instructions).
Here are the six cell types whose two capacity figures appear in the retained set, with the two quotients that follow from them. Every figure in the first three columns is printed; the fourth and fifth columns are my arithmetic.
| Cell | C5 capacity (Ah) | C120 capacity (Ah) | C5 as share of C120 | Current at C5 ÷ current at C120 |
|---|---|---|---|---|
| SUN+ 50 | 45 | 50 | 90.0 per cent | 21.6 |
| SUN+ 100 | 95 | 100 | 95.0 per cent | 22.8 |
| SUN+ 250 | 235 | 250 | 94.0 per cent | 22.56 |
| SUN+ 505 | 470 | 505 | 93.07 per cent | 22.34 |
| SUN+ 960 | 890 | 960 | 92.71 per cent | 22.25 |
| SUN+ 1830 | 1,700 | 1,830 | 92.90 per cent | 22.30 |
The five-hour rate retains between 90.0 and 95.0 per cent of the 120-hour figure, a spread of five percentage points, and the ratio moves with the cell rather than with the chemistry. So the honest statement is not "a nickel-cadmium cell delivers 92 per cent of its capacity at five hours". It is "this cell delivers 90.0 per cent and that cell delivers 95.0 per cent, and you have to read your own row".
There is a good check on this: three cells — SUN+ 100, SUN+ 960 and SUN+ 1830 — appear in two different retained documents, and both documents print identical pairs. The technical manual of June 2012 gives 95 and 100; the installation instructions give 95 and 100. That is what a per-cell property should look like across two printings eleven years apart, and it is the reason to trust the arithmetic that follows rather than the prose around it.
A reader who has seen a competitor's catalogue may object that every battery maker prints a capacity-versus-time table, so where is the finding. The finding is the next column over. The charging current in the installation sheet is defined as "0.1 C5 A", and for SUN+ 960 it is printed as 89 amperes. 0.1 × 890 = 89, exactly. The charger is sized off the five-hour column, not off the nominal one. Whatever the table calls nominal, the operating instruction treats the smaller number as the operative one.
The number the buyer actually spends
A facility engineer does not buy ampere-hours. He buys minutes at a load. The load is in amperes, the catalogue is in ampere-hours, and the bridge between them is the rate — which is why the current column above matters more than the capacity column.
Run that ratio across the six printed pairs and it comes out at 21.6, 22.8, 22.56, 22.34, 22.25 and 22.30. Even the current ratio is a per-cell property: a band of 21.6 to 22.8 times, not a constant of the chemistry. So a buyer comparing two strings by their ampere-hour figures is comparing two durations, neither of which his own load will draw, and the factor that converts one into the other is not a factor at all. It is a row in a table he has to look up.
That is not a scandal. Lookup is cheap, and the maker printed the row. But it explains a procurement argument that recurs wherever standby plant is specified: two bids arrive, one quoting 1,830 ampere-hours and one quoting 1,700, and the lower number wins a comparison that should never have been made in that unit. The figures are the same cell.
The temperature is a band, not a point
My second correction concerns the room. The rating temperature is not 25 °C. It is +20 °C for Uptimax, with the datasheet's amperes valid over +20 °C ± 5 °C, and it is a range of +20 °C to +25 °C for Sunica.plus. Twenty-five degrees is the top of one band and the middle of the other's stated range, which is to say the number I had in my head is not written down as a rating condition anywhere in the set.
The derating is a family of curves, not a number. Figure 1 of the solar manual is captioned "Temperature de-rating: standard electrolyte for operating temperatures from -20°C to +40°C (-4°F to +104°F)", and its legend reads "De-rating factors to apply on RT performance according to temperature and end voltage", with four curves labelled End voltage 1.14 V, 1.16 V, 1.18 V and 1.20 V. Figure 2 covers the special electrolyte down to -40 °C and switches the curve family from end voltage to discharge rate, with curves at 0.005 C A, 0.01 C A, 0.015 C A, 0.02 C A and 0.03 C A at a 1.14 V end voltage.
Uptimax does the same thing per cell range: Figure 1(a) gives "Temperature de-rating factors for L type cell for cell final voltage 1.00 V" and Figure 1(b) the M type at the same final voltage, over −20 °C to +40 °C, with the rates split into a five-hour rate and a one-hour rate for the L type and a 30-minute rate for the M type.
So the derating exists, is labelled, and is drawn. What it is not, in the retained text, is extractable. The curve values live in the drawing, and the extracted text gives the axes and the legend. Across the whole set there is exactly one temperature factor that can be read as a number: the 0.95 at +40 °C that the worked example spends on the 1.16 V curve. The only temperature value a reader of the text can quote is the one a worked example needed in order to be a worked example.
One more line from the 2007 edition belongs here, because it is the sentence that makes the whole derating question a rate question: "The effect of temperature is more marked at higher rates of discharge." The heavier the rate, the more the temperature matters — which means the family that is rated at five hours is the family whose published derating is steepest, and it is also the family a switchgear or UPS duty draws on.
The end voltage is a decision, not a constant
The third condition is the one the site owns rather than the maker. The rating is defined to a cut-off of 1.0 volt per cell. The temperature-derating figures are drawn at four end voltages, and the four labels are 1.14 V, 1.16 V, 1.18 V and 1.20 V. None of those four labels is 1.0 V.
Read that against the rating sentence once more. Capacity is rated to a 1.0 volt cut-off. The derating factor that scales capacity for temperature is drawn for cut-offs between 1.14 V and 1.20 V, which are the cut-offs a real inverter with a real DC bus and a real cable drop will actually reach. The manual has printed the correction for the room and the correction for the cut-off on the same figure, and the cut-off it corrects towards is not the cut-off it rates to.
The worked example shows how this is meant to be used. It computes its own end voltage rather than accepting one: "End voltage is 41.8 V / 36 cells = 1.16 V." 41.8 ÷ 36 = 1.161, which the manual prints as 1.16. A 36-cell string on a 41.8 volt bus is a 1.16 volt per cell cut-off, and 1.16 V is one of the four labelled curves. Whether the curves extend below 1.14 V is not established by the retained text; the four labels are the four the legend carries.
The one page that multiplies
Now the countercase, which is the strongest thing in the set and which I will print as the class-level answer rather than as a caveat.
The solar manual does perform the join. Once, in full, for one cell type, with five printed operands. The requirement is five amperes for 192 hours, which is 960 ampere-hours unadjusted. Then:
we will use a factor of 0.7 (70 % of initial capacity)
because full autonomy is required at the end of life; a charge adjustment of 0.95; "The temperature adjustment value = 0.95 (Figure 1: + 40°C/+ 104°F)"; and a design margin of "0.9 as allowance for a load growth of 10 %". Then the division:
the calculated battery capacity is 960 Ah / (0.7 x 0.95 x 0.95 x 0.9) = 1688.4 Ah
and the equivalent current, and the selection:
the equivalent load current is 1688.4 Ah / 192 h = 8.8 A
8 A / 192 h / 1.16 V = SUN+ 1830 (1 string is required)
The arithmetic closes. 0.7 × 0.95 × 0.95 × 0.9 = 0.568575, and 960 ÷ 0.568575 = 1,688.4 ampere-hours to four significant figures. 1,688.4 ÷ 192 = 8.794, printed as 8.8. The four factors and the requirement produce the stated answer, and the stated answer selects a cell that exists. Anyone who claimed the factors are never multiplied together in one place has not read clause 9 of this manual, and I was that reader for the first hour of this piece.
Two details inside the example are worth their own paragraphs, because they are where the machine shows its seams.
The first: the selection line uses 8 amperes where the calculation above it produced 8.8. That is a difference of 0.8 amperes, or 9.1 per cent of 8.8. It is not an error; it is the derivation ending in a table lookup, where the reader rounds his equivalent current down onto a printed column and reads across. But it means the worked example's own last line is a human step, and a reader who follows the arithmetic rather than the conclusion will land on a slightly heavier duty than the example chose.
The second is the rate. The example's duty is 192 hours — eight days. The cell it selects is a C120 cell. So the only place in the set where the factors are multiplied is a sizing exercise whose own discharge time is lighter than the cell's rating, and the rate correction it needs is small. The heavy-rate buyer, the one for whom the five-hour column exists, gets a column and an example that does not use it. Whether Uptimax contains a worked example at all is not established by the retained set: its manual names the method and prints no arithmetic.
That asymmetry is the piece. The factor machinery is built for the light-rate application. The heavy-rate application gets a second column and a set of curves, and has to do its own multiplication.
The divisor that is a calendar with the years removed
Here is the fattest target in the set, and it is not a missing number. It is a present number with a missing unit.
The example divides by 0.7, and the manual explains the 0.7 twice. The first explanation is the discharge adjustment: 0.7 is "70 % of initial capacity". The second is a figure note, "Life time criteria: Capacity = 70 % of rated capacity", tied to "the number of cycles before reaching a capacity of 70 %". So 0.7 is an end-of-life capacity, and the sizing rule is: install enough cells that the string still meets the duty when it has worn down to seven tenths.
Now put that beside the ageing rule the same manual prints:
the general rule of thumb when considering the aging characteristic of nickel-cadmium is that is will lose approximately 1% of its capacity per year at temperatures less than or equal +25°C (+77°F)
One per cent of rated capacity per year. Seventy per cent remaining. The division is not printed anywhere, and it is two lines of arithmetic: 100 to 70 at one point a year takes thirty years, and 100 to 80 takes twenty. Both are my divisions. The manual prints the rate and the percentage and never the years.
Thirty years is a long time. It is longer than the service-life figure the same company prints for its other stationary nickel-cadmium family, which is twenty years and better:
Uptimax builds on this heritage by ensuring a 20-year plus service life at +25°C (+77°F). Even at +35°C (+95°F), its lifetime falls by just 20% compared with a 50% reduction for a lead-acid battery. (Uptimax datasheet)
And twenty years is what the 80 per cent ending gives at one per cent a year. Which is to say the set contains a life claim that matches a 20 per cent ageing allowance and a sizing criterion that implies a 30 per cent one, both about nickel-cadmium, in documents that never cite each other. The thirty-year figure appears in none of the ten documents.
The two framings of the same allowance are also both printed, in one company, in two buildings. A conference paper whose retained title names its author as a Saft America engineer states the ageing factor as a multiplier rather than the manual's divisor:
If 80% is chosen as the end-of-life point for a Ni-Cd battery, the same 1.25 aging factor would be used. If a lower end-of-life capacity of, say, 70% is chosen, the aging factor would be 1.43. (Aging Factors in Battery Sizing)
1 ÷ 0.8 = 1.25 exactly. 1 ÷ 0.7 = 1.4286, printed as 1.43. The paper's two factors are the manual's two percentages turned upside down, and the paper is helpful enough to say where the factor attaches: "to the calculated capacity (or the number of positive plates), and not to the discharge time". The same paper puts the conventional allowance at "increasing the required capacity by 25%" and names the two standards — IEEE 485 for lead-acid, IEEE 1115 for nickel cadmium — that the Uptimax manual also names as its method.
Choosing 70 per cent instead of 80 per cent therefore installs 14.3 per cent more capacity for the same duty, since 1.4286 ÷ 1.25 = 1.1429. A buyer who has been sold a 1.25 factor and a buyer who has been sold a 0.7 divisor are 14.3 per cent apart on installed plant, and neither of them was told which end of life the number describes in years.
What the float takes back
There is a third age state in this product line, and it is the one the published amperes belong to.
The Uptimax manual is explicit that the performance tables are not beginning-of-life figures: "the tabular data is based upon cell performance after several months of floating", and again, "The performance data sheets for Uptimax are based upon several months' floating and so are for fully float charged cells." The effect it is describing has a shape and a duration:
When a nickel-cadmium cell is maintained at a fixed floating voltage over a period of time, there is a decrease in the voltage level of the discharge curve. This effect begins after one week and reaches its maximum in about 3 months.
and a cure that is not available at the panel:
It can only be eliminated by a full discharge/charge cycle, and it cannot be eliminated by a boost charge.
The datasheet says "after prolonged float charge", which is the same claim without the duration. So the set now contains three ages for one product: the table's age (several months on float), the life criterion's age (70 per cent of rated capacity), and the datasheet's age (twenty years and more at +25 °C). Nothing in the retained set says how the first relates to the second, and the calendar from "several months" to "seventy per cent" is exactly the calendar that is missing.
That matters because the floating effect is easy to confuse with ageing and is not the same thing. It is a voltage-level loss that a full cycle reverses; ageing is a capacity loss that a full cycle does not reverse. A site that commissions a string, discharges it once on acceptance test, and then floats it for three months has already moved to the state the table describes. A site that reads the table's amperes as a first-day figure is reading a number that was measured after the loss it is worried about.
What was read, and what was not
Every absence in this article is a count over ten documents read on 26 November 2026, and the ten are listed at the end. Four of them are Saft product manuals for two nickel-cadmium families; one is an installation and operating instruction set; two are datasheets of 2023; two are the manufacturer's own documentation index pages; one is a conference paper whose retained title names its author and his affiliation. It is not a claim that a figure is unpublished anywhere, and an unopened document is not an empty one.
Three of the ten sources carry less weight than the rest, and the difference is stated here rather than buried. The Uptimax datasheet answered with a 403 when its own PDF was requested, so its life and temperature sentences are quoted from search text rather than from a page this desk opened. The two documentation index pages could not be opened at all; their retained snippets list document rows and nothing technical, so nothing technical is attributed to them beyond the fact that they are the indexes.
The May 2007 solar manual and the installation sheet were returned as page text rather than opened PDFs; their clause text is clear, their curve values are not.
Two printing problems in the set are recorded and adopted by neither. SUN+ 1215 is given 2,800 cubic centimetres of water in one table and 2,700 in another. And the Uptimax rating sentence cites IEC 62259 alone in the 2010 edition and both IEC 62259 and IEC 60623 in the later one, while the five conditions in the sentence itself never change.
The June 2012 solar manual file carries two document blocks, 21817-2-0612 and 21884-2-0414, so the edition of the whole hosted file cannot be stated with confidence; statements above are attributed to the block they appear in. And the identifier 21817-2-0612 appears in the retained titles of both a solar manual and the Uptimax technical manual, a collision this piece does not resolve and does not need to.
What none of that touches is the finding. The rate conversion is a column. The temperature derating is a drawing with one quotable value. The end-voltage family is drawn at four cut-offs, none of which is the rating cut-off. The factors are multiplied once, for a light-rate duty. And the ageing allowance is printed as a percentage in two framings, with the years behind it printed nowhere.
If you are buying a stationary battery this year, the question that follows is one sentence long, and it is not about ampere-hours. Ask which end-of-life capacity the sizing factor describes, and how many years at your battery-room temperature the maker expects that capacity point to be reached. Every number needed to answer is already printed, except the second one. The percentage is a specification you can test at delivery. The year is the part you live with.
Sources
- Sunica.plus Ni-Cd batteries for PV systems, technical manual, June 2012
- Sunica.plus technical manual, May 2007
- Sunica.plus installation and operating instructions
- Sunica.plus datasheet, February 2023
- Uptimax technical manual, June 2010
- Uptimax technical manual, 2012 edition with 2018 cover
- Uptimax datasheet, January 2023
- Saft Sunica.plus product and documentation page
- Saft Uptimax product and documentation page
- Aging Factors in Battery Sizing
Member Briefing
Read the full trend briefing
Members read the full briefing with the source notes behind every finding.
Strategic Circle
A daily briefing in your language, built from changes we have verified.
Join for USD 20/monthCancel anytime.
Members also get the full research library, a daily briefing on the networks they follow and the private forum.