Summary

  • Ameren Missouri's Large Load Customer Service rate triggers at 75 MW of monthly maximum demand where the statute behind it says 100 MW of annual peak, bills demand per kilowatt at $22.43 summer and $10.66 winter, and states an on-peak window, an off-peak credit and an 80 per cent floor — but no averaging interval at all.
  • The 2026 integrated resource plan counts the same class in gigawatts and in two disagreeing pairs of growth rates, then sets accredited capacity against a summer reserve margin printed as 7.9 per cent in one chapter and 8.9 per cent in its own appendix; no reviewed page converts any of those counts into the tariff's own unit.

On 4 January 2026 a rate schedule took effect in Missouri that answers, for the first time, what the state's largest utility will charge the buildings now arriving. Union Electric Company, which files with the Commission as Ameren Missouri, calls it Large Load Customer Service, Service Classification No. 11(M). It applies to any new facility whose peak load forecast is reasonably expected to reach a monthly maximum demand of 75 MW at any time during its term, and to expansions that add 75 MW over pre-existing demand (tariff, Sheet 61.6).

The number in the statute is not that number. Section 393.130.7 RSMo requires electric corporations serving more than 250,000 customers to file schedules for customers reasonably projected above an annual peak demand of 100 MW. The Commission's order approving the plan prints both figures and says which it took: the approved plan "requires a lower monthly maximum demand than Senate Bill 4, is designed to capture more customers" (order, File No. ET-2025-0184). Two thresholds, two units, one class — 100 MW of annual peak in the statute, 75 MW of monthly maximum demand in the tariff, with the Company free to aggregate premises and meters to reach it (stipulation, Exhibit 601).

That pair is not a drafting slip; it is the first appearance of the pattern this article is about. Missouri answers one load in several instruments, and the instruments do not convert.

The kilowatt is priced. The hour is not defined.

Demand is billed "per kW of Billing Demand", $22.43 in summer and $10.66 in winter. Billing demand in any month is the highest demand established during on-peak hours or fifty per cent of the highest demand established off-peak, whichever is highest, but never less than eighty per cent of the Contract Capacity in the service agreement — the sheet calls that the Minimum Billing Demand. On-peak runs 6:00 A.M. to 10:00 P.M. daily.

What the sheet does not print is the averaging interval. Not fifteen minutes, not thirty, not sixty. Nothing on that page states how long a demand must be sustained before it becomes a billed kilowatt.

The omission looks less like carelessness when set beside the same company's Missouri standby rider, which defines demand as the "maximum 15 minute demand established during peak hours or 50% of the maximum 15 minute demand established during off-peak hours, whichever is greater", with a floor of 5,000 kW for Large Primary Service (Rider SS). The interval is in Ameren's drafting vocabulary. It did not travel into the rate written for the largest customers in the state.

The settlement behind the tariff shows the company can produce that interval on another occasion: large-load customers owe an updated quarterly peak demand forecast by 1 September each year, and in rate cases the company supplies load data "hourly and at 15-minute demand intervals upon request". A fifteen-minute measurement exists as a reporting obligation. It does not exist as a billing determinant.

Here the reading has to be graded. The tariff arrived as extracted text, and a neighbouring sheet not captured could carry the definition. What can be said precisely is this: the sheet that governs both eligibility and billing demand, read on 26 November 2026, states a billing rule, two rate periods and a floor, and states no interval.

The same class grows in gigawatts

The plan counts it in another unit altogether. The 2026 integrated resource plan describes its Large Load Tariff class as data centres, customers above 75 MW of monthly peak demand, and forecasts class sales growing 20.5 per cent a year and class demand 14.0 per cent a year from 2027 to 2046, with low and high demand growth of 11.6 and 16.4 per cent (Chapter 2, Planning Environment). Chapter 3 gives the same class 20.0 per cent energy and 13.1 per cent peak growth, beside 1.2 per cent energy and 0.6 per cent peak for everyone else (Chapter 3, Load Analysis). Two chapters, two pairs of growth rates, one class.

The absolute figures sit in Chapter 1: 2.8 GW of expected demand from signed electric service agreements by 2030, against 1.5 GW by 2032 in the prior plan; 5 GW by 2035 and 6 GW by 2046 in the base case; 6 GW by 2035 and 9 GW by 2046 in the high case (Chapter 1, Executive Summary). Five gigawatts is 5,000 MW, which is 66.7 times the 75 MW eligibility threshold; 6 GW is 80 times and 9 GW is 120 times. That multiplication is mine. It is also the only way this reading can get from the plan's unit to the tariff's, because no reviewed page performs it: no page converts a gigawatt of plan increment into a count of 75 MW customers.

The capacity side then adds a third unit. The plan builds its baseline capacity position from the seasonal peak forecast with no large-load additions, plus seasonal MISO reserve requirements, plus existing plant unforced capacity and wind, solar and battery accreditations, with build thresholds of 300 MW summer and 550 MW winter set by subtracting 200 MW from extreme-weather requirements (Chapter 9). Accredited capacity is printed by season and year: 7,899 MW summer in 2026 declining to 2,748 MW from 2043, 6,460 MW winter declining to 2,929 MW, with spring at 8,050 MW and fall at 8,029 MW in 2026 (Chapter 4 Appendix B).

The reserve margin is printed twice

The requirement that these megawatts must satisfy is a percentage, and the plan prints it twice. Footnote 6 of Chapter 2 explains that a 7.9 per cent summer planning reserve margin applied to a 7,172 MW normal summer peak underlies its rounded figure of approximately 500 MW of extra extreme-weather load and reserve. That footnote's own operands make 566.6 MW, not 500: the gap is 66.6 MW. The Chapter 2 appendix, describing the same MISO study, lists summer at 8.9 per cent beside fall 16.3, winter 23.5 and spring 29.2 (Market Price Scenarios); at 8.9 per cent the same 7,172 MW peak requires 638.3 MW, which is 71.7 MW above the first reading.

Put the plan's two perimeters together and the arithmetic is short. The 7,172 MW normal summer peak plus the 566.6 MW that 7.9 per cent requires is 7,738.6 MW against 7,899 MW of summer accredited capacity in the same plan — about 160 MW of headroom for 2026, before a single large-load addition is counted. That subtraction is mine; the perimeters are the plan's forecast peak and the plan's accredited capacity, and no reviewed page performs it.

Four counts of one load

Four counts of one load
Count Unit Where printed What it measures
Eligibility 75 MW monthly maximum demand Tariff, Sheet 61.6; order Whether the rate applies
Billing demand kW, interval unstated Tariff, Sheet 61.6 What the customer pays for
Plan increment GW by year; per cent growth IRP Chapters 1, 2, 3, 9 What the utility expects to serve
Accredited capacity Seasonal MW under a PRM IRP Chapters 4B, 2, 2A, 9 What must exist to serve it

Four counts, four purposes, one load. None of the four is wrong. The loading dock of this subject is that no page in the set states the conversion between them, and the conversion that would join the second row to the third is the one thing a data-centre load makes easy: its shape.

Why the shape is the whole argument

A campus that draws steady power holds firm capacity at its full draw through every hour the system peaks, and delivers comparatively little energy per unit of that capacity. Claim that the load factor is near unity and the tariff's own arithmetic turns into a per-megawatt-hour price you can read off the sheet. A flat 75 MW for a year is 657,000 MWh. Six summer months at $22.43 and six winter months at $10.66 on 75,000 kW is $14,890,500 a year at the eligibility floor, which divides to $22.66 per megawatt-hour — the summer demand rate itself, because one megawatt-hour per megawatt-hour is what a flat load means.

Hold the same 75 MW peak and halve the energy, and the same annual demand charge is $45.33 per delivered megawatt-hour. Those three figures are mine, on an even six-and-six split of the tariff seasons; the load factor sets the per-megawatt-hour price of capacity, not the rate.

That is the question the sheet answers without saying so. Its shape assumptions are a floor and a credit: 80 per cent of Contract Capacity is billable in a month the campus barely runs — 60 MW at a 75 MW contract — and off-peak demand counts at half value. A near-unity load never touches the off-peak credit and never falls near the floor. The tariff is built to be paid by a flat load, and states no assumption about how flat.

Three countercases deserve testing rather than dismissing. The dedicated class exists, with a stated minimum demand charge, a twelve-year minimum term, an optional five-year ramp, automatic five-year extensions absent thirty-six months' notice, collateral of two years' minimum bills and revenue sharing; so the allocation question is answered at class level and left open at the level of the delivered megawatt-hour (order; Commission index). Contractually interruptible load would state the coincidence assumption outright; no reviewed page makes large-load service interruptible, and the stipulation instead obliges the customer not to exceed Contract Capacity without Company authorisation and reliability verification. And a later sheet may carry the interval the main sheet omits. None of the three closes the gap identified here.

Who pays, and what the plant is for

The stake is not abstract. Ameren Missouri's plan projects 5 GW of large-load demand by 2035 against a current supply of roughly 10 GW, and the Office of Public Counsel's senior counsel attributes the primary driver of the proposed 2,100 MW West Alton gas plant — in service by 2031, among Missouri's first candidates for construction-work-in-progress financing — to the increase in large-load customers, primarily data centres, while non-large-load demand rises 1.2 per cent (reported by St. Louis Public Radio). One 75 MW campus is 0.75 per cent of that 10 GW, and 1.5 per cent of the 5 GW the plan expects within a decade. My arithmetic again, and the point of it is scale: the tariff's threshold is small against the plan's increment, so the count of customers behind the gigawatts is large, and every one of them is billed by a definition whose interval is unwritten.

A developer comparing states is therefore comparing demand definitions, not prices; a household on the same system is paying for capacity held by a load billed on a different clock; and a commission approving a forecast approves a number whose conversion into customer arithmetic sits in another document, or in none.

What this reading covers

This is a reading of twelve documents captured on 26 November 2026, listed below; an absence here is a count over that set and date. All twelve arrived as extraction, and none was opened end to end in a browser.

Numeric tables in Chapter 2 and the large-load annual peak table in Chapter 3 did not render, so reserve and class values come from prose and footnotes rather than those tables; Figures 9.2 and 9.3 are charts; the accredited-capacity years in Appendix B were paired by inference from the row header sequence; the stipulation text was truncated in places; Rider SS governs standby service and is evidence of drafting convention only; and the St. Louis Public Radio report is secondary, used here for the policy stakes and one attributed position.

No page in the set prints a load factor, an IT-load definition, or a billing interval for large-load demand.

Sources

BTW's key story established that Missouri's buildout had become a power question — Missouri becomes test case for power-driven hyperscale buildout. This piece asks a narrower one: which unit the utility answers in, and whether the answer is printed where a customer could read it.