Summary

  • The published 32,760 overall ssj_ops/watt is one column of operations divided by one column of watts across eleven load levels, and the eleventh level produces zero operations while adding 57.3 W to the denominator. Adding the printed cells gives 32,765.9, so a stranger can recompute the headline without asking anyone for the raw data.
  • Every row enters that quotient with weight equal to its own wattage, which makes the score a power-weighted mean of the eleven per-level efficiencies. Strike the idle row and the Windows score rises 2.79 per cent, 3.6 times the 0.78 per cent that separates Lenovo's Windows and Linux records on the same SR655 V3.

The page that performs the division and prints neither sum

The result page for the ThinkSystem SR655 V3 on Microsoft Windows Server 2022 opens with the number and closes its results block with the same number expressed as an expression: "∑ssj_ops / ∑power = 32,760". Between those two lines sit eleven rows, each with a target load, a count of ssj_ops, an average active power in watts and a per-row ratio. Add the column of ssj_ops yourself and you get 69,736,482. Add the column of watts, including Active Idle, and you get 2,128.3. Divide the first by the second and you get 32,765.9. The published score is that quotient, and the result page prints neither of its two operands as a total.

This is worth pausing on, because the missing sums are the whole argument. A reader who wants to know what the score is made of has to do the benchmark's addition for it. A reader who does not has been handed a four-digit figure with no visible structure at all, on a page that looks like a specification table and reads like a verdict. The same page prints the processor, the memory, the operating system, the Java build, the boot firmware version, every BIOS setting the lab changed, the room temperature at each load level, the model and serial number of the power analyser and the date it was last calibrated.

It prints everything about the instrument except the two totals the instrument's readings were added into.

The definition tells you to add the column that contains a row of nothing

The rules that govern the metric are published by the Standard Performance Evaluation Corporation. Section 3.1 of the run and reporting rules says it in one sentence: "Overall ssj_ops/watt represents the sum of the performance measured at each target load level (in ssj_ops) divided by the sum of the average power (in W) at each target load including active idle." The user guide says the same thing in slightly different words and names the unit "overall ssj_ops / watt". Both sentences specify two additions and one division, and both specify that the second addition runs over a list that includes a load level at which the machine is idle.

What that load level is, the benchmark's methodology note describes as one of eleven measurement intervals at 100, 90, 80, 70, 60, 50, 40, 30, 20 and 10 per cent of maximum throughput, followed by Active Idle, "represented by a 0% throughput measurement". The FAQ is blunter still: Active Idle is "the eleventh load level", its performance value is zero, its power is measured at what is usually the lowest consumption rate, and it is treated the same as all other load levels when the overall score is computed.

So the definition is not a mistake and not a trick. It is a deliberate choice, made in the open, that a machine's resting draw belongs in the efficiency figure at full weight, and that a row which performs no transactions is one of the eleven rows the figure averages.

The score is a mean, and every row votes with its watts

Here is the part that takes one line of algebra and is printed nowhere. The quotient is the number of operations summed over the schedule divided by the watts summed over the schedule. That is the same thing as a weighted average of the eleven per-row efficiencies, where the weight of a row is its own share of the summed watts. A row that draws a lot of power and performs few operations drags the figure down in proportion to the power it draws. A row that draws a lot of power and performs many operations pulls it up correspondingly. A row that draws power and performs nothing contributes only the drag.

On the SR655 V3 those weights are easy to read off the table. The 100 per cent row draws 319 W out of 2,128.3 W, so it casts 15.0 per cent of the vote. The 10 per cent row draws 115 W, so it casts 5.4 per cent. The Active Idle row draws 57.3 W, so it casts 2.69 per cent of the vote while producing no operations whatsoever. The best row on the page, 41,257 ssj_ops/W at 80 per cent load, is not the score and is not close: it is 1.26 times the published figure, because 80 per cent load carries 246 W of a 2,128.3 W budget rather than the whole of it.

The 100 per cent row, which carries the largest weight of all, is 3.8 per cent less efficient than that peak: 39,685 ssj_ops/W against 41,257.

This is why the arithmetic of the headline and the arithmetic of the column disagree. Take the eleven printed per-level ratios and average them without weights: 28,262.5. The published score is 15.9 per cent above that plain average of its own rows. Nobody is hiding the rows; they are printed side by side with the score. But the score is not the average of what is printed beside it, and the sentence that says so would have to explain the weighting, and the weighting is the schedule.

What the idle row is worth

Divide the summed operations by the summed watts of the ten load rows alone and the SR655 V3 returns 33,672.9. That is 2.79 per cent above the published 32,760, and the difference is entirely the 57.3 W of a row that produced nothing. In the denominator that row is 2.69 per cent of the watts; in the numerator it is nothing at all; the difference between those two facts is the 2.79 per cent.

The second Lenovo submission in the same quarter lets you check whether that is a property of one machine or of the method. The ThinkSystem SR650 V3, a two-socket Intel system, published its own result two days earlier at 15,112 overall ssj_ops/watt. Its ten load rows sum to 82,589,223 ssj_ops over 5,302 W; add the Active Idle row at 163 W and the denominator becomes 5,465 W; the quotient is 15,112.4, against a printed 15,112. Remove the idle row and the figure rises to 15,576.9, which is 3.08 per cent above the printed score, from a row that is 2.98 per cent of the watts and none of the operations.

Two different machines, two different vendors' worth of heat, and the idle row costs the first 2.79 per cent and the second 3.08 per cent. The unweighted mean of the eleven printed ratios sits 15.9 per cent below the headline on the first and 14.2 per cent below it on the second. The numbers differ; the structure does not. This is the method talking, not the machine. What does differ is the hardware: the SR655 V3 returns 2.17 times the SR650 V3's 15,112, a gap wide enough to survive every subtlety in this piece.

Two tables, printed on the result pages, with the arithmetic I performed on their cells:

What the idle row is worth
Target load SR655 V3 ssj_ops SR655 V3 W SR655 V3 ssj_ops/W
100% 12,659,391 319 39,685
90% 11,449,655 292 39,253
80% 10,133,493 246 41,257
70% 8,883,440 227 39,053
60% 7,562,011 212 35,675
50% 6,351,376 193 32,879
40% 5,083,978 175 28,970
30% 3,796,974 156 24,404
20% 2,547,302 136 18,680
10% 1,268,862 115 11,032
Active Idle 0 57.3 0
What the idle row is worth
Target load SR650 V3 ssj_ops SR650 V3 W SR650 V3 ssj_ops/W
100% 14,922,488 915 16,315
90% 13,532,724 808 16,747
80% 12,021,350 674 17,838
70% 10,536,243 574 18,364
60% 9,021,458 508 17,774
50% 7,518,039 453 16,588
40% 6,017,662 405 14,844
30% 4,511,532 363 12,441
20% 3,004,408 322 9,320
10% 1,503,319 280 5,363
Active Idle 0 163 0

Two records on one chassis, 0.78 per cent apart

Lenovo announced the Windows result under the heading "ThinkSystem SR655 V3 Sets World Record with New SPECPower on Windows Benchmark Result" and printed the category it had won in a single sentence: "Best score on a 1-processor, 2U rack system running Microsoft Windows Server." The announcement is dated 10 July 2023, reports 32,760 overall ssj_ops/watt, links the SPEC result, and prints no per-load row, no sum and no run condition.

Four days earlier the same model had been submitted to the same benchmark under a different operating system. The Linux result is 33,014 overall ssj_ops/watt on SUSE Linux Enterprise Server 15 SP4, on the same one-socket SR655 V3, with the same Java build, and Lenovo wrote that one up too, in a second announcement with the same construction: world record, on Linux, published 10 July 2023.

The gap between them is 254 points, which is 0.78 per cent of the Windows score. That is the entire measurable effect of the variable Lenovo's record category is named after. The row that does no operations, in the same submission, is worth 2.79 per cent. The idle row is 3.6 times the operating system.

Read the category in the other direction too. A record scoped by processor count, form factor and operating system is not a claim about efficiency; it is a claim about a filing cabinet drawer. The same company filed a second winning entry in the drawer next door, for the same box, four days earlier. Both are true. Neither is a fact about the machine that a buyer would recognise as one, because the machine is not what the category varies and the schedule is not what the number measures.

The conditions a legal run must meet, and the things the submitter chooses

The rules leave a lot fixed. Section 2.3.2 says the workload runs unconstrained for at least three calibration intervals, then at 100, 90, 80, 70, 60, 50, 40, 30, 20 and 10 per cent of maximum throughput, then in an idle interval with no Java transactions, and that the sequence "must not be changed". Section 2.5.2 fixes the measurement interval at 240 seconds and allows each load point's actual interval to fall between 238.8 seconds (−0.5 per cent) and 242.4 seconds (+1.0 per cent).

Section 2.13.2 requires an analyser that reports true RMS power plus at least two of voltage, current and power factor, with an overall uncertainty of 1 per cent or better over the ranges measured, a current crest factor of at least 3, and calibration within the past year traceable to NIST or a counterpart national metrology institute.

Section 2.9 sets the environment: ambient temperature 20 degrees Celsius or above, elevation and humidity within the system's documented operating specification, with the validator demanding that the minimum temperature reading be at least 20 degrees Celsius from the start of the run through the end of Active Idle, including calibration. Humidity need not be reported. There is a floor and, in the text of the rules as read, no ceiling.

Then there is the list of things the rules do not fix, all of which sit in the same document as the score. The SR655 V3 submission records Custom Mode, SVM, SMEE and SRIOV disabled, memory at 4000 MHz, SOC P-states at P3, NPS4, the L1 and L2 stream prefetchers and the L1 region prefetcher disabled, and Core Performance Boost disabled, plus Windows power settings PROCTHROTTLEMIN 0, PROCTHROTTLEMAX 100, PERFEPP 0 and perfautonomous 1, with four logical processors per JVM.

The SR650 V3 submission records Operating Mode Efficiency, Flavor Power, memory at Minimal Power, Turbo Mode enabled, SNC4, the same prefetchers disabled, 120 JVM instances and a 1500 MB heap. The ambient minimum on the first is 21.8 degrees Celsius, 1.8 K above the floor; on the second it is 21.2 degrees Celsius, 1.2 K above it. The second machine's Yokogawa WT210 was calibrated on 7 May 2023 and its test date was 15 May 2023, eight days later.

Every one of those choices is disclosed, legal and consequential. A machine tuned for its sleeping state and a machine tuned for its busy state are two different submissions of the same box, and both are correct entries in the same drawer. The benchmark publishes the tuning so that a reader can judge whether two scores were made the same way. Neither Lenovo announcement repeats a word of it.

The rows a real server lives in

The low-load rows are the ones a machine that is not being benchmarked spends its life in, and they are terrible by the headline's standard. On the SR655 V3 the 10 per cent row returns 11,032 ssj_ops/W, which is 33.7 per cent of the headline. Its draw is 115 W, and the idle row that isn't in that row's schedule draws 57.3 W, or 49.8 per cent of it. On the SR650 V3 the 10 per cent row returns 5,363 ssj_ops/W, 35.5 per cent of the headline, and the 163 W of Active Idle is 58.2 per cent of that row's 280 W.

None of this makes the published figure wrong. It makes the published figure a description of a load profile, and the profile is a straight line down from full throttle to nothing, with the nothing charged at the price of the something. A procurement that compares two servers on overall ssj_ops/watt is comparing two means whose heaviest weights sit at the two ends of a schedule: full load, where every vendor tunes hard because the press release lives there, and idle, where the press release never looks but the denominator does.

A procurement that wants to know what a machine costs to run at 30 per cent load can read the 30 per cent row, and it is printed; but nobody quotes it, because it is not the record.

What the number automates

The metric automates one operation: the division of two sums that the submitter has already chosen the terms of. The page performs the division, prints the result, and prints the eleven rows the division ran over without ever printing the totals. The vendor's page copies the result and attaches a noun: world record, for a 1-processor 2U rack system running Microsoft Windows Server. The reader receives a categorical claim, backed by a proportion, computed from a schedule nobody has seen.

Where does the measured performance meet deployment? On the page, the answer is: at eleven points on a line the benchmark drew, in a room one to two degrees above the minimum the rules allow, on a machine configured and tuned by the party that will quote the score. That is a perfectly respectable place for a measurement to meet a workload, as long as everyone agrees it is a place and not a property. The category Lenovo won is a place too: a drawer defined by socket count, height and an operating system worth less to the number than the row that does nothing.

The same question in other clothes

Any published ratio whose denominator is a sum over a schedule has this structure, and the same three questions prise it open. Who wrote the schedule? Which row in it produces nothing, or nearly nothing, and how heavily is that row weighted? Is the figure an average of the rows or a ratio of their sums, and if it is a ratio, which rows dominate it?

A vehicle's test-cycle fuel economy, a battery's discharge rating, a pump's wire-to-water efficiency, a data centre's power usage effectiveness: each of them divides something by a sum of something else taken over a sequence of states that a standard, not the buyer, chose. Each of them has a state in which the input is paid and the output is not. Each of them can be recomputed from its own published rows by anyone who is willing to add a column two times and divide once, and each is almost always quoted as though it were a single measurement taken off a single instrument.

The SPECpower case is unusually clean because the rows are printed, the rule that makes them one number is one sentence, and the vendor printed a category whose boundary you can price to three significant figures against the idle row. It is the same trick with the arithmetic left visible.

What twelve documents do not settle

The rules page carries the line "Last updated: May 18 2015" while a PDF version of the rules surfaced with a later revision date; which revision governs a 2023 result is not settled by the documents read here, and the rule text quoted above is the text as published at the address cited. No upper temperature bound appears in the rules as retrieved, and humidity need not be reported, so the environmental envelope is a floor with no printed ceiling; how much score a warmer room would buy or cost cannot be computed from these pages.

No page in the set defines a second aggregate metric that excludes Active Idle, so the cost of the idle row can be computed but never quoted; section 3.3.3's per-load ratios are per-row figures, not an alternative aggregate. No deployment measurement of either machine outside the benchmark schedule appears in the set, so where the eleven load levels sit relative to any real customer's traffic is not documented here. Only one vendor's results were read, so the "world record" is a category claim that these twelve documents cannot cross-check against a field.

And the two sources date the same result differently: the SPEC page carries publication on 7 July 2023, Lenovo's announcement says the benchmark result was published on July 1, 2023, and neither explains the difference.

What the documents do settle is smaller and harder: the definition, the eleven steps, the zero in the last row, the weights those watts hand out, the 2.79 per cent they cost one machine and the 3.08 per cent they cost another, and the 0.78 per cent that separates two records held by one chassis in two operating systems. The division is printed on the page. Its operands are not. That is the whole of the claim, and it is enough to change how the number should be read.