Summary
- Commission Delegated Regulation (EU) 2024/1364 admits a data centre to Europe's reporting scheme at 500 kW of installed information technology power demand, which Article 2(14) defines as the sum of the nominal power demand of network, server and storage equipment in the computer room floor area — a nameplate figure the operator writes into the return.
- The efficiency ratios published under the same act are computed from metered energy at boundaries Annex II fixes, and in the eight documents read for this article no provision of the 2024 regulation names a party obliged to check the declared figure before those ratios are built on it.
The door is a nameplate. Commission Delegated Regulation (EU) 2024/1364, adopted on 14 March 2024 and published in the Official Journal on 17 May 2024, admits a data centre to the first phase of the common Union rating scheme at 500 kW, and Article 2(14) says precisely what that number is: the sum of the nominal power demand, in kilowatts, of the network or networks, servers and storage installed in the data centre computer room floor area (consolidated text; Official Journal text). The bibliographic record gives the adoption date, the Official Journal citation and the European Legislation Identifier (act record). Nominal power demand is what a device's rating plate declares it can draw. The operator adds those plates together, writes the total into a return, and the total decides whether the facility is inside the scheme at all.
The ratios are metered. Article 4 sends the sustainability indicators to Annex III, which prints four quotients: power usage effectiveness as E_DC divided by E_IT, water usage effectiveness as W_IN divided by E_IT with IT energy in megawatt-hours, energy reuse factor and renewable energy factor as reused or renewable energy divided by E_DC (consolidated text). Those are metered quantities, and Annex II fixes where the meter sits. Total data-centre energy is measured at the input of the system, before the supply transfer switchgear, at the primary supply, the secondary supply and every additional supply including back-up generation. IT equipment energy is measured at every uninterruptible power system connected to IT equipment, or at the power distribution unit under the category 2 method where there is no uninterruptible system. Water is every volume entering the boundary. Waste heat counts only where it is handed off outside the boundary, with heat reused internally for cooling subtracted. Renewable totals follow CEN/CENELEC EN 50600-4-3, and guarantees of origin count only where the reporting centre owns and retires them. Annex II also requires a record of the measurement points and devices to be kept for at least ten years (consolidated text; Official Journal text).
So the scheme runs on two kinds of number. Whether you are in is decided by a nameplate sum. How well you did is decided by meters. Hold the two apart, because the published page does not.
The two clocks in the Directive behind it. Article 33(3) of Directive (EU) 2023/1791 empowered the delegated act and required the first one by 31 December 2023 (Article 33); the act was adopted on 14 March 2024, seventy-four days later, counted from the two printed dates and therefore my arithmetic, not the Commission's. Article 12(1) of the same Directive told Member States to require operators above 500 kW to make their Annex VII information publicly available by 15 May 2024 (Article 12). The regulation that fixes what those indicators are reached the Official Journal on 17 May 2024, two days after the date Member States were meant to have started making them public. The Directive's own identity — adopted 13 September 2023, published in Official Journal L 231 of 20 September 2023 — sits on its EUR-Lex record (Directive record). Both article texts are read here from a legal publisher's article-level reproduction, because the EUR-Lex record of the Directive ended in its recitals and never reached Article 12; the limit belongs beside the claim, so it is beside it.
What the world is shown. Article 5(2) requires the reported information, the key performance indicators and the Annex III indicators to be made public in an aggregated manner at Member State and Union level, in accordance with Annex IV (consolidated text). Annex IV then prints the list: the number of reporting data centres, their distribution by size category, their total installed information technology power demand, their total energy consumption, their total water consumption, and average power usage effectiveness, water usage effectiveness, energy reuse factor and renewable energy factor (consolidated text). The averages are not simple means. The act requires a weighted metric aggregation using total energy consumption as the weighting factor. Breakdowns by type and by size appear only where the category holds at least three data centres.
Read that list again, because it holds the article. One entry in it — total installed information technology power demand, summed over the reporting population — is denominated in the nameplate kilowatts that decided who was admitted. The four entries beside it are metered and weighted by metered energy. The published page therefore puts its taxonomy and its ratio on two measurement bases, and in the documents read here it does not say so.
Who checks. Article 5(3) reads, in full: "Member States shall have access to all information and key performance indicators communicated to the European database by data centres in their territory pursuant to Article 3" (consolidated text). That is access. It is not a duty to check, and no other provision read here adds one. Article 5(5) then keeps each individual return confidential, and recital 12 reaches that conclusion through the trade and business secrets carve-out in Article 12(1) of the Directive and the aggregated-level publication in Article 12(3).
The route matters as much as the duty. Article 3(1) sends the return through a national reporting scheme if the Member State where the data centre is located has established such a scheme, and otherwise straight to the European database (consolidated text). Where no such scheme exists, the return travels from the operator to the register with nothing in between.
And the Commission's own directorate describes the result in a phrase it does not source: the dashboard presenting the aggregated data, it says, is "updated monthly to include any data that has been submitted and validated by EU countries" (DG Energy). The same page records a July 2025 report analysing the data submitted in the 2024 reporting period. The validation sentence carries no article number.
The legal text that does describe the check is the amending delegated regulation adopted on 21 September 2026. Its recital 7 says the database allows national competent authorities to verify which data centres communicated information and key performance indicators, as well as the quality of those reports, before submitting the data to the Commission. Recital 9 says the Commission should send Member States a list of logical and conditional checks, so that those checks are performed by the national reporting schemes, in case such a scheme exists in a Member State, before the data go to the database (amending act).
Count the dates. Three annual reporting deadlines had closed before that act was adopted — 15 September 2024, 15 May 2025 and 15 May 2026 — and the third was 129 days before the adoption, counted from the printed dates, again mine. The channel the checks are routed through is the channel the 2024 act made optional.
The honest counterweight. Annex IV is not silent about coverage. It requires the number of reporting data centres to be published beside the totals, which is more than many statistical surfaces ever admit. But the count is denominated in the adjective: every total beside it is scoped to the reporting population, and no page in the eight documents read for this article prints the population that fell inside the 500 kW scope. The count therefore has no denominator, and the three-facility floor blanks the smallest categories entirely. A reader can see how many facilities were efficient. A reader cannot see how many were counted and did not report.
Why this is not the DORA piece, or the AI Act piece. Those two read when an obligation bites: the intervals of a notification duty, and the dates of a staged regime. This one reads where the number is taken. The instrument does not fail to count. It counts what it is told, checks the arithmetic, publishes the mean, and leaves the ten-year file of measurement points standing in the operator's own building.
What would settle it. Produce a page in this set that prints the number of data centres inside the 500 kW scope, or a national scheme that checks a submitted figure before it is submitted, and this finding collapses. Produce neither, and what Europe has published is a ratio whose denominator was declared, whose numerator was metered, and whose inputs no named outsider has been given the duty to read. The control recommendation follows from the act's own Annex IV rather than from any suspicion about any operator: print the in-scope count beside the reporting count, mark which published columns are nameplate figures and which are metered, name the party that performs the logical and conditional checks, and record the reasons a facility in scope gave for not reporting — or state plainly that the regime does not collect them.
The eight documents read on 24 and 25 November 2026 are the regulation in consolidated and Official Journal form, its act record, the Directive record, two article-level reproductions, the Commission's directorate page and the 2026 amending act; two further Commission addresses that appeared to cover the subject returned no readable content that day and support nothing here. Nothing in this article asserts that any operator misreported a figure, or that any Member State failed to check one. The finding is about where the duty was put.
Member Briefing
Read the full trend briefing
Members read the full briefing with the source notes behind every finding.
Strategic Circle
A daily briefing in your language, built from changes we have verified.
Join for USD 20/monthCancel anytime.
Members also get the full research library, a daily briefing on the networks they follow and the private forum.